Lightning Protection With a Differentiated Configuration of Arresters in a Distribution Network

被引:12
作者
Cao, Jinxin [1 ]
Du, Yaping [1 ]
Ding, Yuxuan [1 ]
Qi, Ruihan [2 ]
Chen, Mingli [1 ]
Li, Zhe [1 ]
Zhao, Xiangen [1 ]
Andreotti, Amedeo [3 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Environm & Energy Engn, Hung Hom, Hong Kong, Peoples R China
[2] China Southern Power Grid, Power Res Inst, Guangzhou 510760, Peoples R China
[3] Univ Naples Federico II, Dept Elect Engn & Informat Technol, I-80123 Naples, Italy
关键词
Lightning; Flashover; Wires; Surges; Load flow analysis; Distribution networks; Arresters; surges; distribution network; overhead line; Monte Carlo method; arresters; DISTRIBUTION LINES; WIRE; PERFORMANCE; LOCATION;
D O I
10.1109/TPWRD.2022.3192482
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
When concerning the installation and operation costs, it is always desirable to protect an overhead distribution network with a limited quantity of surge arresters (SAs). This paper presents a novel procedure for designing differentiated protection against lightning, by identifying appropriate positions for those SAs on the overhead line. Rather than the traditional flashover rate of a whole line, indices in terms of flashover numbers at individual poles and associated with possible stroke locations are introduced in this paper. Based on these flashover indices, a differentiated configuration of SAs can be identified using a selection strategy. After several rounds of selection, a differentiated SA protection scheme can be obtained, given by a pre-set quantity of SAs. In this procedure, a simplified probability-based approach is proposed to determine the flashover indices. By comparing the traditional Monte Carlo method, this approach can achieve a 10-fold increase in computational efficiency with reasonable accuracy. Two different selection strategies are introduced in this paper. Compared with the selection strategy using the flashover indices at individual poles, the selection strategy based on a group of poles is recommended because it yields a configuration with better lightning performance with the same quantity of SAs. This design procedure is applied to practical distribution networks with a shield wire and nearby structures. The influence of grounding impedance, a shield wire, and nearby structures is addressed. Finally, a generalized step-by-step procedure is provided to assist in a differentiated SA protection design.
引用
收藏
页码:409 / 419
页数:11
相关论文
共 31 条
[1]  
Anderson R.B., 1980, ELECTRA, V69, P65
[2]  
[Anonymous], 2010, 500612010 GB
[3]  
[Anonymous], 2006, C4402 CIGRECIRED JWG, V287
[4]  
[Anonymous], 2021, CIGRE WG C4.23
[5]  
[Anonymous], 1991, 33 CIGRE WG 01 SC
[6]  
[Anonymous], 2011, 154742011 IEEE, P1, DOI [DOI 10.1109/IEEESTD.2011.5960751, 10.1109/IEEESTD.2011.5692956, DOI 10.1109/IEEESTD.2011.5692956, DOI 10.1109/IEEESTD.2011.5706451]
[7]   Indirect-Lightning Performance of Overhead Distribution Networks With Complex Topology [J].
Borghetti, Alberto ;
Nucci, Carlo Alberto ;
Paolone, Mario .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) :2206-2213
[8]   Practical Schemes on Lightning Energy Suppression in Arresters for Transformers on 10 kV Overhead Distribution Lines [J].
Cao, Jinxin ;
Du, Yaping ;
Ding, Yuxuan ;
Qi, Ruihan ;
Li, Binghao ;
Chen, Mingli ;
Li, Zhe .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (05) :4272-4281
[9]   Comprehensive Assessment of Lightning Protection Schemes for 10 kV Overhead Distribution Lines [J].
Cao, Jinxin ;
Du, Yaping ;
Ding, Yuxuan ;
Qi, Ruihan ;
Li, Binghao ;
Chen, Mingli ;
Li, Zhe .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) :2326-2336
[10]   Lightning Surge Analysis of Transmission Line Towers With a Hybrid FDTD-PEEC Method [J].
Cao, Jinxin ;
Du, Yaping ;
Ding, Yuxuan ;
Li, Binghao ;
Qi, Ruihan ;
Zhang, Yang ;
Li, Zhe .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (02) :1275-1284