Unlocking demand response in commercial buildings: Empirical response of commercial buildings to daily cooling set point adjustments

被引:38
作者
de Chalendar, Jacques A. [1 ]
McMahon, Caitlin [1 ]
Valenzuela, Lucas Fuentes [2 ]
Glynn, Peter W. [3 ]
Benson, Sally M. [1 ]
机构
[1] Stanford Univ, Dept Energy Resources Engn, Stanford, CA 94305 USA
[2] Stanford Univ, Dept Elect Engn, Stanford, CA 94305 USA
[3] Stanford Univ, Dept Management Sci & Engn, Stanford, CA 94305 USA
关键词
Commercial building flexibility experiments; Data -driven building energy models; Thermal demand response; Temperature set point experiments; Commercial HVAC flexibility potential; Grid -interactive efficient buildings; HVAC; TEMPERATURE; SIMULATION; EFFICIENCY; SYSTEM;
D O I
10.1016/j.enbuild.2022.112599
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Buildings represent over half of global electricity demand. Cooling buildings already accounts for over 9% of global electricity demand and is expected to grow rapidly due to climate-change induced hot-spells and increasing prosperity in developing economies. In the US, commercial buildings represent 35% of nationwide electricity consumption. Increased electricity demand for cooling services will challenge already stressed power grids, particularly during times of peak demand. This work explores the flexibility and demand response potential of large Heating, Ventilation and Air Conditioning (HVAC) systems based on an extensive set of measurements from six commercial buildings in a Warm-summer Mediterranean climate. Over a three-month summer period, zone-level temperature set points were adjusted daily in six commercial buildings to determine the effect on chilled water and electricity loads, as well as on zonelevel temperatures. External weather conditions were measured continuously during the testing period. The experimental data that were collected are published with this article. These experiments confirmed the potential to provide flexibility by reducing energy demands based on modest zone-level temperature set point adjustments. A two-degree Fahrenheit increase of the cooling set point resulted in a 13-28% reduction in daily building-level cooling loads on average for four office buildings and 3-4% for two laboratory buildings. The impact on electric loads was less than 2% (excluding for cooling water but including for ventilation). Zone-level temperature increases were measurable but temperatures remained within the target ranges. By collecting 385 experiment-days of experiment data, we were able to parameterize statistical models for the response of the buildings. These models provide statistical guarantees on the reliability of thermal demand response. This work provides a blueprint for constructing building and zone-level energy-response functions and highlights the value of testing buildings repeatedly and across a range of weather conditions. Providing statistical performance guarantees will be critical for widespread adoption of demand response technology to provide the flexibility needed to meet peak electricity demands. Combined with thermal storage, the daily flexibility studied here would also unlock daily and sub-daily electrical flexibility, and can also be integrated with sub-daily flexibility from building-level electrical loads.(c) 2022 The Author(s). Published by Elsevier B.V. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
引用
收藏
页数:13
相关论文
共 38 条
[21]   An open-source automated continuous condition-based maintenance platform for commercial buildings [J].
Katipamula, Srinivas ;
Gowri, Krishnan ;
Hernandez, George .
SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (04) :546-556
[22]  
Keskar A., 2022, ENV RES INFRASTRUCT
[23]  
Kiliccote Sila., 2010, FINDINGS 7 YEARS FIE
[24]   Assessing the Potential to Reduce U.S. Building CO2 Emissions 80% by 2050 [J].
Langevin, Jared ;
Harris, Chioke B. ;
Reyna, Janet L. .
JOULE, 2019, 3 (10) :2403-2424
[25]   Simulation and experimental demonstration of model predictive control in a building HVAC system [J].
Li, Pengfei ;
Vrabie, Draguna ;
Li, Dapeng ;
Bengea, Sorin C. ;
Mijanovic, Stevo ;
O'Neill, Zheng D. .
SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2015, 21 (06) :721-733
[26]  
Liu J., 2020, ACEEE SUMMER STUDY E
[27]  
Ma YD, 2012, IEEE CONTR SYST MAG, V32, P44, DOI 10.1109/MCS.2011.2172532
[28]   A Critical Exploration of the Efficiency Impacts of Demand Response From HVAC in Commercial Buildings [J].
MacDonald, Jason S. ;
Vrettos, Evangelos ;
Callaway, Duncan S. .
PROCEEDINGS OF THE IEEE, 2020, 108 (09) :1623-1639
[29]   Building commissioning: a golden opportunity for reducing energy costs and greenhouse gas emissions in the United States [J].
Mills, Evan .
ENERGY EFFICIENCY, 2011, 4 (02) :145-173
[30]  
Motegi N, 2007, LBNL59975, P4