Bubbling Phenomena in Liquid-Filled Transformers: Background and Assessment

被引:6
作者
Gmati, Ghada [1 ]
Rao, Ungarala Mohan [1 ]
Fofana, Issouf [1 ]
Picher, Patrick [2 ]
Arroyo-Fernandez, Oscar [2 ]
Rebaine, Djamal [1 ]
机构
[1] Univ Quebec Chicoutimi, Dept Appl Sci, Saguenay, PQ G7H 2B1, Canada
[2] Hydroquebecs Res Inst, Varennes, PQ J3X 1S1, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
transformers; insulation; bubbling; moisture; mineral oil; ester liquids; MOISTURE DIFFUSION-COEFFICIENTS; HIGH-VOLTAGE TRANSFORMERS; MIXED INSULATING LIQUIDS; POWER TRANSFORMER; MATHEMATICAL-MODEL; PART; OIL; PAPER; EVOLUTION; CELLULOSE;
D O I
10.3390/en16093829
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The degradation of the insulation system in liquid-filled power transformers is a serious concern for electric power utilities. The insulation system's ageing is accelerated by moisture, acids, oxidation products, and other decay particles (soluble and colloidal). The presence of these ageing by-products is detrimental to the insulation system and may further lead to premature ageing and serious consequences. The ageing mechanisms of oil-paper insulation are complex, highly interrelated, and strongly temperature-dependent. The operating temperature of the transformer insulating system has a direct relationship with the loading profile. The major aspect that is witnessed with the fluctuating temperatures is moisture migration and subsequent bubble evolution. In other words, gas bubbles evolve from the release of water vapor from the cellulosic insulation wrapped around the transformer windings. The models presented in the existing standards, such as the IEC Std. 60076-7:2018 and the IEEE Std. C57.91:2011, are mainly based on the insulation temperature, which acts as a key parameter. Several studies have investigated the moisture dynamics and bubbling phenomenon as a function of the water content in the paper and the state of the insulation system. Some studies have reported different prototypes for the estimation of the bubble inception temperatures under selected conditions. However, there are various attributes of the insulation system that are to be considered, especially when expanding the models for the alternative liquids. This paper reviews various evaluation models reported in the literature that help understand the bubbling phenomenon in transformer insulation. The discussions also keep us in the loop on the estimation of bubbling behavior in alternative dielectric liquids and key attributable factors for use in transformers. In addition, useful tutorial elements focusing on the bubbling issue in transformers as well as some critical analyses are addressed for future research on this topic.
引用
收藏
页数:23
相关论文
共 95 条
[11]  
Ding H., 2017, P IEEE 19 INT C DIEL, P1, DOI [10.1109/icdl.2017.8124640, DOI 10.1109/ICDL.2017.8124640]
[12]   Moisture equilibrium in transformer paper-oil systems [J].
Du, Y ;
Zahn, M ;
Lesieutre, BC ;
Mamishev, AV ;
Lindgren, SR .
IEEE ELECTRICAL INSULATION MAGAZINE, 1999, 15 (01) :11-20
[13]  
Du Y, 1998, 1998 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, P341, DOI 10.1109/CEIDP.1998.734013
[14]  
Fan X., 2021, CSEE J. Power Energy Syst., early access, V7, P1, DOI [10.17775/cseejpes.2021.00510, DOI 10.17775/CSEEJPES.2021.00510]
[15]   Comparative evaluation of alternative fluids for power transformers [J].
Fernandez, Inmaculada ;
Ortiz, Alfredo ;
Delgado, Fernando ;
Renedo, Carlos ;
Perez, Severiano .
ELECTRIC POWER SYSTEMS RESEARCH, 2013, 98 :58-69
[16]   A REFINED MATHEMATICAL-MODEL FOR PREDICTION OF BUBBLE EVOLUTION IN TRANSFORMERS [J].
FESSLER, WA ;
ROUSE, TO ;
MCNUTT, WJ ;
COMPTON, OR .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) :391-404
[17]   Challenge of mixed insulating liquids for use in high-voltage transformers, part 2: Investigations of mixed liquid impregnated paper insulation [J].
Fofana, I ;
Wasserberg, V ;
Borsi, H ;
Gockenbach, E .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (04) :5-16
[18]   Challenge of mixed insulating liquids for use in high-voltage transformers, part 1: Investigation of mixed liquids [J].
Fofana, I ;
Wasserberg, V ;
Borsi, H ;
Gockenbach, E .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (03) :18-31
[19]  
Fofana I., 2013, P CIGRE 2013 CAN C W, P1
[20]   MATHEMATICAL AND EXPERIMENTAL-ANALYSIS OF THE FIELD DRYING OF POWER TRANSFORMER INSULATION [J].
FOSS, SD ;
SAVIO, L .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (04) :1820-1828