Life-Based Geometric Design of HVDC Cables-Part 2: Effect of Electrical and Thermal Transients

被引:6
作者
Diban, Bassel [1 ]
Mazzanti, Giovanni [1 ]
Seri, Paolo [1 ]
机构
[1] Alma Mater Studiorum Univ Bologna, Dept Elect Elect & Informat Engn DEI, I-40136 Bologna, Italy
关键词
Transient analysis; Power cables; Voltage; HVDC transmission; Power cable insulation; Steady-state; Electric fields; Cable design; high voltage; high-voltage direct-current (HVdc) transmission; life estimation; power cables; power system transients; EXTRUDED CABLE; HIGH-VOLTAGE; RELIABILITY; OVERVOLTAGES;
D O I
10.1109/TDEI.2022.3212974
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study, in two parts, investigates the design of high-voltage direct-current (HVdc) cables depending on electrothermal life modeling of the insulating material. The first part investigated the way in which different parameters affect the design of an HVdc cable in steady-state conditions, i.e., with known nominal voltage and ampacity. This article investigates the effect of electrical (i.e., voltage) transients, such as voltage polarity reversals (VPRs), in addition to thermal transients (such as load cycles of cable current) on the electrothermal life map of HVdc cables, and their influence on cable feasibility. An ad hoc MATLAB code has been developed for this study. The results show a considerable negative effect of electrical transients on the expected life. A more severe effect of electrical transients is noticed for materials with a lower value of the temperature coefficient of conductivity, due to a longer duration of transients. On the contrary, thermal transients associated with load cycles-which mostly imply current values equal to or lower than cable ampacity-imply insulation temperature values always lower than the maximum permissible temperature, and thus, they have a positive effect on the electrothermal life since the thermal stress applied on the cable insulation will be reduced, allowing for smaller cable geometries for a fixed voltage and ampacity rating. It must be noticed that only the electrothermal life is investigated in this article, and other types of stresses (e.g., mechanical stress) may also affect insulation life, but this is out of the scope of this study.
引用
收藏
页码:97 / 105
页数:9
相关论文
共 33 条
  • [1] 50Hertz Transmission GmbH
  • [2] Amprion GmbH
  • [3] Tennet TSO GmbH
  • [4] TransentBw GmbH, 2019, GRID DEV PLAN GDP 20, V2nd
  • [5] Testing Challenges in the Development of Innovative Extruded Insulation for HVDC Cables
    Albertini, M.
    Bononi, S. Franchi
    Giannini, S.
    Mazzanti, G.
    Guerrini, N.
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2021, 37 (06) : 21 - 32
  • [6] [Anonymous], 2008, 608532 IEC
  • [7] Battaglia A, 2019, C ELECT INSUL DIEL P, P442, DOI [10.1109/ceidp47102.2019.9010572, 10.1109/CEIDP47102.2019.9010572]
  • [8] Influence of soil humidity on the thermal impedance, time constant and structure function of underground cables: A laboratory experiment
    Chatzipanagiotou, Panagiotis
    Chatziathanasiou, Vasilis
    De Mey, Gilbert
    Wiecek, Boguslaw
    [J]. APPLIED THERMAL ENGINEERING, 2017, 113 : 1444 - 1451
  • [9] Diban Bassel, 2022, 2022 IEEE 4th International Conference on Dielectrics (ICD), P13, DOI 10.1109/ICD53806.2022.9863466
  • [10] The effect of temperature and stress coefficients of electrical conductivity on the life of HVDC extruded cable insulation subjected to type test conditions
    Diban, B.
    Mazzanti, G.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (04) : 1313 - 1321