A sensitive single-end DC line fault detection method for MMC-HVDC grids using reactor voltage ratio

被引:7
|
作者
Yu, Senlin [1 ]
Wang, Xiaoru [1 ]
Zhang, Xiao-Ping [2 ]
机构
[1] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu 610031, Sichuan, Peoples R China
[2] Univ Birmingham, Dept Elect Elect & Syst Engn, Birmingham B15 2TT, England
关键词
MMC-HVDC grid; Line -mode voltage; Transient voltage; Mathematical morphology; High -resistance faults; NONUNIT PROTECTION; TRANSMISSION-LINES; SYSTEMS; IDENTIFICATION; SCHEME; WAVE;
D O I
10.1016/j.ijepes.2023.108953
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The fast, sensitive, and reliable primary protection method can ensure the continuous and reliable operation of the modular multilevel converter (MMC)-based HVDC grid during dc faults. This paper proposes a fault detection method based on the ratio of voltage integrals to improve the single-end method sensitivity to high-resistance faults. First, the reactor line-mode transient voltage caused by the initial traveling wave (TW) is analyzed in the fault component network. The exponential term of the voltage is independent of the fault resistance and can be reflected by the proposed voltage integral ratio. Next, the influence of subsequent TWs on the integral is analyzed. The partition time, selected by the mathematical morphology, is proposed to divide the voltage sampling data into two parts. Finally, the criterion using the ratio of the two-part voltage integral is proposed to detect internal faults. The +/- 500 kV bipolar MMC-HVDC grid built on PSCAD/EMTDC validates that the pro-posed method can fast identify internal faults, and the protected zone covers the whole line length. Smulation cases analyze the influence of the reactor and sampling frequencies on the proposed method. Moreover, the method is sensitive to high-resistance faults and can work under white noise and different wiring modes.
引用
收藏
页数:11
相关论文
共 28 条
  • [21] A Single-end Method for Fault Section Estimation in Distribution Network Using Wavelets
    Ye Lei
    Song Yuan-chao
    Li Cheng-huang
    Wu Ling
    AUTOMATIC CONTROL AND MECHATRONIC ENGINEERING III, 2014, 615 : 208 - +
  • [22] Multi-Layer Model Enabled Fault Location for Underground Cables in MMC-HVDC Grids Considering Distributed and Frequency Dependent Line Parameters
    Lu, Dayou
    Liu, Yu
    Xie, Jiahao
    Wang, Binglin
    Liao, Qifeng
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (04) : 3082 - 3096
  • [23] A Novel DC Fault Ride-Through Method for Wind Farms Connected to the Grid Through Bipolar MMC-HVDC Transmission
    Jiang, Shouqi
    Xin, Yechun
    Li, Guoqing
    Wang, Lixin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (06) : 2937 - 2950
  • [24] Non-Unit Ultra-High-Speed DC Line Protection Method for HVDC Grids Using First Peak Time of Voltage
    Zhang, Chenhao
    Song, Guobing
    Dong, Xinzhou
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) : 1683 - 1693
  • [25] Single-ended DC Fault Location Method For MMC-Based HVDC Power System Using Adaptive Multi-step Levenberg-Marquardt Algorithm
    Liu, Le
    Xie, Fan
    Popov, Marjan
    Hao, Zhiguo
    Lekic, Aleksandra
    2023 IEEE BELGRADE POWERTECH, 2023,
  • [26] Single-end traveling wave protection method in flexible DC transmission line based on dominant frequency attenuation characteristics
    Deng, Feng
    Zhang, Zhen
    Zhong, Hang
    Zeng, Xiangjun
    Huang, Yifei
    Zeng, Zhe
    Feng, Sixu
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 152
  • [27] A Novel Single-Terminal Fault Location Method for AC Transmission Lines in a MMC-HVDC-Based AC/DC Hybrid System
    Xue, Shimin
    Lu, Junchi
    Liu, Chong
    Sun, Yabing
    Liu, Baibing
    Gu, Cheng
    ENERGIES, 2018, 11 (08):
  • [28] A High Speed Single-Ended Fault-Detection Method for DC Distribution Line-Part II: Protection Scheme
    Song, Guobing
    Chang, Zhongxue
    Zhang, Chenhao
    Kazmi, Sayed Tassawar Hussain
    Zhang, Wei
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (03) : 1257 - 1266