Modeling and multi-objective optimization of polymer desiccant cooling system

被引:3
作者
Zhang, Hui [1 ]
Qian, Zheng [1 ]
Fang, Zhicong [1 ]
Zhang, Xuemei [1 ]
机构
[1] Tongji Univ, Sch Mech Engn, Shanghai 201804, Peoples R China
关键词
Air conditioning; Dehumidification; PDWS; NSGA II; PERFORMANCE; ALGORITHM;
D O I
10.1016/j.csite.2023.103871
中图分类号
O414.1 [热力学];
学科分类号
摘要
The polymer desiccant cooling system (PDCS) efficiently reduces energy consumption compared to the vapor compression system (VCS). In this paper, a PDCS integrated heat pump is proposed. Experimental and simulation are used to analyze the performance of the PDCS. The control strategy is optimized with the NSGA II algorithm. A case study in Shanghai illustrates the practical application of the PDCS optimization strategy. The calculation results based on the thermal comfort requirement show the maximum energy consumption of optimized PDCS, routine PDCS, and VCS are 549.9 kW, 597.7 kW, and 1327.7 kW. About 62.7 % and 72.3 % of energy can be saved in routine PDCS and optimized PDCS compared to VCS. Moreover, the maximum moisture removal efficiency of the above scenarios is 10.67 kW/(g center dot s), 11.56 kW/(g center dot s), and 25.42 kW/(g center dot s), separately. Additionally, the maximum coefficient of performance is 0.530, 0.457, and 0.182, respectively.
引用
收藏
页数:16
相关论文
共 30 条
  • [1] Comparative analysis of a new desiccant dehumidifier design with a traditional rotary desiccant wheel for air conditioning purpose
    Abdelgaied, Mohamed
    Saber, Mohamed A.
    Bassuoni, M. M.
    Khaira, Ahmad M.
    [J]. APPLIED THERMAL ENGINEERING, 2023, 222
  • [2] Multi-objective Optimization of Electrochemical Machining of Hardened Steel Using NSGA II
    Acharya, Biswesh R.
    Mohanty, Chinmaya P.
    Mahapatra, S. S.
    [J]. CHEMICAL, CIVIL AND MECHANICAL ENGINEERING TRACKS OF 3RD NIRMA UNIVERSITY INTERNATIONAL CONFERENCE ON ENGINEERING (NUICONE2012), 2013, 51 : 554 - 560
  • [3] Multi objective optimization of performance of three-heat-source irreversible refrigerators based algorithm NSGAII
    Ahmadi, Mohammad Hossein
    Ahmadi, Mohammad Ali
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 60 : 784 - 794
  • [4] Characterization and cost analysis of a modified silica gel-based adsorption desalination application
    Alsaman, Ahmed S.
    Askalany, Ahmed A.
    Ibrahim, E. M. M.
    Farid, A. M.
    Ali, Ehab S.
    Ahmed, M. Salem
    [J]. JOURNAL OF CLEANER PRODUCTION, 2022, 379
  • [5] Composite material-based a clay for adsorption desalination and cooling applications
    Alsaman, Ahmed S.
    Ibrahim, E. M. M.
    Askalany, Ahmed A.
    Farid, A. M.
    Ali, Ehab S.
    Ahmed, M. Salem
    [J]. CHEMICAL ENGINEERING RESEARCH & DESIGN, 2022, 188 : 417 - 432
  • [6] Experimental investigation of porous carbon for cooling and desalination applications
    Alsaman, Ahmed S. S.
    Ahmed, M. Salem
    Ibrahim, E. M. M.
    Ali, Ehab S. S.
    Farid, A. M.
    Askalany, Ahmed A. A.
    [J]. NPJ CLEAN WATER, 2023, 6 (01)
  • [7] Experimental assessment of the energy performance of a hybrid desiccant cooling system and comparison with other air-conditioning technologies
    Angrisani, Giovanni
    Roselli, Carlo
    Sasso, Maurizio
    [J]. APPLIED ENERGY, 2015, 138 : 533 - 545
  • [8] A MOPSO algorithm based on pareto dominance concept for comprehensive analysis of a conventional adsorption desiccant cooling system
    Bouchaala, Ahmed
    Merroun, Ossama
    Sakim, Anas
    [J]. JOURNAL OF BUILDING ENGINEERING, 2022, 60
  • [9] Research of a rotary desiccant wheel based hybrid air conditioning system with natural cold source
    Chen, Liu
    Yu, Zhuolei
    [J]. 10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 492 - 496
  • [10] Abnormal energy consumption detection using ensemble model for water chilling unit on HVAC system
    Cheng, Hengda
    Liu, Zheng
    Chen, Luyao
    Chen, Huanxin
    [J]. ENERGY AND BUILDINGS, 2023, 297