摘要
In this article, the influence of splitting a local underfloor air distribution system (UFAD) on indoor thermal comfort for three occupants was studied numerically. A validated computational fluid dynamics (CFD) model was employed in this investigation. The proposed heating system was evaluated and analyzed for different values of air temperature and supply velocity. Providing suitable thermal comfort and saving energy are considered the main evaluation indexes for this study. Three cases, cases 2, 3, and 4, of the proposed local UFAD system were compared with a traditional heating system case, case 1. The supplying air velocity and air temperature in the reference case were 0.5 m/s and 29 degrees C, while in cases 2, 3, and 4, they were 0.4 m/s and 29 degrees C, 28 degrees C, and 27 degrees C, respectively. The results show that acceptable indoor human thermal comfort and energy demand reduction were achieved by using the splitting UFAD concept.
引用
收藏
页数:17
相关论文
共 32 条
[1]  
Ahmed A.Q., 2021, Int. J. Appl. Sci. Eng., V18, P1
[2]  
Al-Shohani Wisam A. M., 2020, IOP Conference Series: Materials Science and Engineering, V881, DOI 10.1088/1757-899X/881/1/012056
[3]   Saving energy by using underfloor-air-distribution (UFAD) system in commercial buildings [J].
Alajmi, Ali ;
El-Amer, Wid .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (08) :1637-1642
[4]   Thermal comfort assessment of an office building served by under-floor air distribution (UFAD) system - A case study [J].
Alajmi, Ali F. ;
Baddar, Faisal A. ;
Bourisli, Raed I. .
BUILDING AND ENVIRONMENT, 2015, 85 :153-159
[5]   A virtual thermostat for local temperature control [J].
Alhashme, Mohamed ;
Ashgriz, Nasser .
ENERGY AND BUILDINGS, 2016, 126 :323-339
[6]  
[Anonymous], 2004, ANSI/ASHRAE Standard 90.1-2004: Energy Standard for Buildings Except Low-Rise Residential
[7]   A comparison of heating terminal units: Fan-coil versus radiant floor, and the combination of both [J].
Atienza Marquez, Antonio ;
Cejudo Lopez, Jose Manuel ;
Fernandez Hernandez, Francisco ;
Dominguez Munoz, Fernando ;
Carrillo Andres, Antonio .
ENERGY AND BUILDINGS, 2017, 138 :621-629
[8]   Floor heating and cooling combined with displacement ventilation: Possibilities and limitations [J].
Causone, Francesco ;
Baldin, Fabio ;
Olesen, Bjarne W. ;
Corgnati, Stefano P. .
ENERGY AND BUILDINGS, 2010, 42 (12) :2338-2352
[9]   Airflow and air temperature distribution in the occupied region of an underfloor ventilation system [J].
Chao, CYH ;
Wan, MP .
BUILDING AND ENVIRONMENT, 2004, 39 (07) :749-762
[10]   Experimental and numerical investigations on stratified air distribution systems with special configuration: Thermal comfort and energy saving [J].
Cheng, Yuanda ;
Niu, Jianlei ;
Liu, Xiaoping ;
Gao, Naiping .
ENERGY AND BUILDINGS, 2013, 64 :154-161