Resilient Wide-Area Damping Control to Mitigate Strong Cyber Attack: A Multiple-Controller Switching Approach

被引:11
|
作者
Zhao, Yifan [1 ]
Yao, Wei [1 ]
Zhang, Chuan-Ke [2 ]
Ai, Xiaomeng [1 ]
Wen, Jinyu [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
[2] China Univ Geosci, Sch Automat, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Switches; Damping; Control systems; Phasor measurement units; Oscillators; Cyberattack; Wind power generation; Wide-area damping control; inter-area oscillation; strong attacks; multiple-controller switching; offshore wind; PREDICTIVE CONTROL; SYSTEM; HVDC; OSCILLATIONS; DESIGN;
D O I
10.1109/TSG.2022.3215785
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The growing risk of cyber attacks targeting wide-area damping control (WADC) has spawned much research on designing attack-resilient controllers recently. However, the issue of attack strength did not get enough attention so that most existing resilient WADCs may fail to defend strong attacks. To address this problem, this paper proposes a multiple-controller switching approach based resilient wide-area damping controller (MCS-RWADC) to suppress inter-area oscillations and mitigate strong attacks. It is inclusive of multiple secure networked prediction control based modules (SNPMs) and a switch-monitor module (MSM). The SNPM can detect attacks, differentiate attack strength and compensate for weak attacks. In terms of strong attacks, multiple SNPMs are implemented to work as backup and three operating states as well as the corresponding switching rules are designed to realize automatic switching among them. MSM is responsible for monitoring the states and directing the switching. Case studies are conducted on a 4-area 5-terminal voltage source converter-based multi-terminal high voltage direct current based offshore wind farm integration system. Simulation results verify MCS-RWADC cannot only suppress the inter-area oscillation but also handle the strong attacks under a wide range of operating conditions with various wind power output.
引用
收藏
页码:2326 / 2337
页数:12
相关论文
共 34 条
  • [1] Quantifying Resilience of Wide-Area Damping Control Against Cyber Attack Based on Switching System Theory
    Zhao, Yifan
    Yao, Wei
    Zhang, Chuan-Ke
    Shangguan, Xing-Chen
    Jiang, Lin
    Wen, Jinyu
    IEEE TRANSACTIONS ON SMART GRID, 2022, 13 (03) : 2331 - 2343
  • [2] Resilient Adaptive Wide-Area Damping Control to Mitigate False Data Injection Attacks
    Zhao, Yifan
    Yao, Wei
    Nan, Jiajun
    Fang, Jiakun
    Ai, Xiaomeng
    Wen, Jinyu
    Cheng, Shijie
    IEEE SYSTEMS JOURNAL, 2021, 15 (04): : 4831 - 4842
  • [3] Resilient Wide-Area Damping Control for Inter-Area Oscillations to Tolerate Deception Attacks
    Yao, Wei
    Nan, Jiajun
    Zhao, Yifan
    Fang, Jiakun
    Ai, Xiaomeng
    Zuo, Wenping
    Wen, Jinyu
    Cheng, Shijie
    IEEE TRANSACTIONS ON SMART GRID, 2021, 12 (05) : 4238 - 4249
  • [4] Wide-Area Damping Control Resilience Towards Cyber-Attacks: A Dynamic Loop Approach
    Patel, Abhilash
    Roy, Spandan
    Baldi, Simone
    IEEE TRANSACTIONS ON SMART GRID, 2021, 12 (04) : 3438 - 3447
  • [5] Cyber-Attack Resilient Design of Wide-Area PSS Considering Practical Communication Constraints
    Prakash, Tapan
    Singh, Vinay Pratap
    Mohanty, Soumya R.
    IEEE SYSTEMS JOURNAL, 2020, 14 (02): : 2012 - 2022
  • [6] Design and Defense of Modal Resonance-Oriented Cyber-Attack Against Wide-Area Damping Control
    Wang, Zhaoyuan
    Bu, Siqi
    IEEE TRANSACTIONS ON SMART GRID, 2024, 15 (02) : 2164 - 2178
  • [7] Resilient Wide-Area Damping Control Using GrHDP to Tolerate Communication Failures
    Shen, Yu
    Yao, Wei
    Wen, Jinyu
    He, Haibo
    Jiang, Lin
    IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (03) : 2547 - 2557
  • [8] Incomplete Information Stochastic Game Theoretic Vulnerability Management for Wide-Area Damping Control Against Cyber Attacks
    Li, Qingyang
    Li, Yang
    Liu, Shichao
    Wang, Xiaozhe
    Chaoui, Hicham
    IEEE JOURNAL ON EMERGING AND SELECTED TOPICS IN CIRCUITS AND SYSTEMS, 2022, 12 (01) : 124 - 134
  • [9] Design of a resilient wide-area damping controller using time delays
    Bento, Murilo E. C.
    ELECTRICAL ENGINEERING, 2025, 107 (01) : 1111 - 1124
  • [10] Online PMU-Based Wide-Area Damping Control for Multiple Inter-Area Modes
    Zenelis, Ilias
    Wang, Xiaozhe
    Kamwa, Innocent
    IEEE TRANSACTIONS ON SMART GRID, 2020, 11 (06) : 5451 - 5461