Failure analysis of copper pipes used in the heat exchangers in fan coil units

被引:1
作者
Sargin, Fatih [1 ]
Kanbur, Kursat [1 ]
Turkmen, Ilyas [1 ]
机构
[1] Manisa Celal Bayar Univ, Met & Mat Engn Dept, Manisa, Turkiye
关键词
Ant-nest corrosion; Copper pipe; Failure analysis; Heat-exchanger; Microstructural analysis; ANT-NEST CORROSION; TEMPERATURE; BEHAVIOR; ALLOYS;
D O I
10.3989/revmetalm.239
中图分类号
TF [冶金工业];
学科分类号
0806 ;
摘要
Heat exchangers (HE) consist of copper and steel pipes and are used for heating and cooling the ambient air. One of the main problems seen in HE is the leakage on copper pipes. In this study, failed and properly working copper pipe samples used for different durations were examined in detail. The microstructural analyses were performed using optical microscopy (OM) and scanning electron microscopy (SEM) to detect corrosion occurrences on copper pipe surfaces. In addition, corrosion products of the samples were de-fined by X-Ray Diffraction (XRD), Energy Dispersive Spectroscopy (EDS) and Fourier-Transform Infrared Spectroscopy (FTIR) analyses. The formation of interconnected tunnels in cross section of the failed copper pipe sample that were in microscopic dimensions and corrosion products were observed. Consequently, all the analyses result that were obtained from the samples pointed out a corrosion mechanism known as ant-nest corrosion. It was concluded that the main reason of corrosion was related to ethylene glycol type additives which were used in HE along with mains water.
引用
收藏
页数:11
相关论文
共 40 条
  • [1] Ant-nest corrosion failure of heat exchangers copper pipes
    Cozzarini, Luca
    Marsich, Lucia
    Schmid, Chiara
    ENGINEERING FAILURE ANALYSIS, 2020, 109
  • [2] A laboratory study of the failure analysis of copper tube used in the air conditioning heat exchanger
    Wang, Zhongqi
    Li, Haihong
    Cheng, Dayong
    Qin, Shiteng
    Li, Deshan
    Zhang, Xintao
    MATERIALS AND CORROSION-WERKSTOFFE UND KORROSION, 2024, 75 (07): : 924 - 931
  • [3] Failure analysis of copper tube used in a refrigerating plant
    Chandra, K.
    Kain, Vivekanand
    Shetty, P. S.
    Kishan, Ram
    ENGINEERING FAILURE ANALYSIS, 2014, 37 : 1 - 11
  • [4] Optimising thermal design for cross flow heat exchanger in fan coil units
    Hassan, Ahmed M.
    Alwan, Adil Abbas
    Hamzah, Hameed K.
    AUSTRALIAN JOURNAL OF MECHANICAL ENGINEERING, 2025, 23 (02) : 391 - 408
  • [5] HEAT TRANSFER ANALYSIS OF SHELL-AND-HELICAL-COIL HEAT EXCHANGERS
    Morris, Anthony Edward
    Wei, C. S.
    Unnthorsson, Runar
    Dell, Robert
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2016, VOL. 8, 2017,
  • [6] An experimental study of frost distribution and growth on finned tube heat exchangers used in air source heat pump units
    Zhang, Long
    Jiang, Yiqiang
    Dong, Jiankai
    Yao, Yang
    Deng, Shiming
    APPLIED THERMAL ENGINEERING, 2018, 132 : 38 - 51
  • [7] Analysis of Designs of Heat Exchangers Used in Adsorption Chillers
    Bujok, Tomasz
    Boruta, Piotr
    Mika, Lukasz
    Sztekler, Karol
    ENERGIES, 2021, 14 (23)
  • [8] Corrosion Failure Analysis on Heat Exchanger Pipes
    Qiankun Z.
    Yafei S.
    Sixian R.
    Huifeng L.
    Xingjiang Z.
    Journal of Failure Analysis and Prevention, 2017, 17 (2) : 349 - 353
  • [9] Failure analysis of a copper tube in a finned heat exchanger
    Peltola, H.
    Lindgren, M.
    ENGINEERING FAILURE ANALYSIS, 2015, 51 : 83 - 97
  • [10] A comprehensive analysis of the reliability indicators for heat exchangers of steam turbine units
    Plotnikov P.N.
    Brodov Yu.M.
    Murmanskii B.E.
    Thermal Engineering, 2007, 54 (2) : 133 - 136