An analytical model for seismic response analysis of electrical equipment-steel support structure

被引:0
作者
Xie, Qiang [1 ]
Liang, Huangbin [1 ]
机构
[1] Tongji Univ, Dept Struct Engn, 1239 Siping Rd, Shanghai 200092, Peoples R China
关键词
Equipment-support coupling system; Analytical model; Seismic response; Shaking table test; Parametric analysis; PERFORMANCE; SYSTEMS;
D O I
10.1016/j.jcsr.2023.108379
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Electrical equipment mounted on supporting structures is typical in a substation but vulnerable to earthquakes from previous field investigations. To evaluate the seismic performance of such an electrical equipment-support coupling system, a modal space analytical model was developed using the vibration partial differential equation (PDE) with distributed parameters and joint nodes. In the analytical model, resonant frequencies and mode shapes were obtained through numerical algorithms based on the boundary condition of each segmented beam. Then seismic responses of the coupling system can be attained by the modal decomposition method and superposition principle. A full-scale shaking table test was conducted on a 550 kV bushing-support coupling structure, and the accuracy of the analytical model was verified by the experimental results. Furthermore, a ceramic breakage inside the connecting flange at the base cross-section of the bushing specimen was observed after the seismic qualification test, which means its seismic performance can not meet the demand in the IEC seismic design specifications. To figure out this problem, parametric analysis was carried out using the analytical model to study the influence of parameters of the supporting structure and flange connection on the seismic responses of the equipment. In light of the analytical results, halving the original flange's flexural rigidity can reduce the bottom stress of the bushing by about 20% without over-magnifying its top displacement for this bushing-support coupling system. Application of the presented analytical modelling method can assist in the seismic optimization design of other equipment-support coupling systems in substations.
引用
收藏
页数:11
相关论文
共 28 条
  • [1] Seismic retrofitting of an HV circuit breaker using base isolation with wire ropes. Part 1: Preliminary tests and analyses
    Alessandri, S.
    Giannini, R.
    Paolacci, F.
    Malena, M.
    [J]. ENGINEERING STRUCTURES, 2015, 98 : 251 - 262
  • [2] Chopra AnilK., 2007, Dynamics of structures: theory and applications to earthquake engineering, V3rd
  • [3] Estimation of displacement at interconnection points of substation equipment subjected to earthquake
    Dastous, JB
    Filiatrault, A
    Pierre, JR
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) : 618 - 628
  • [4] Eidinger J., 2012, M 9 0 TOHOKU EARTHQU
  • [5] Seismic response of transformer-bushing systems
    Ersoy, S
    Saadeghvaziri, MA
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) : 131 - 137
  • [6] Seismic response of high voltage electrical transformer-bushing systems
    Filiatrault, A
    Matt, H
    [J]. JOURNAL OF STRUCTURAL ENGINEERING, 2006, 132 (02) : 287 - 295
  • [7] Influence of supporting frame on seismic performance of 1100-kV UHV-GIS bushing
    He, Chang
    Xie, Qiang
    Yang, Zhenyu
    Xue, Songtao
    [J]. JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2019, 161 : 114 - 127
  • [8] International Electrotechnical Commission (IEC), 2016, IEC TS 61463-2016
  • [9] Japan Electric Association (JEA), 2011, JEAG 5003-2010
  • [10] Seismic Response of High-Voltage Transformer-Bushing Systems Incorporating Flexural Stiffeners II: Experimental Study
    Koliou, Maria
    Filiatrault, Andre
    Reinhorn, Andrei M.
    [J]. EARTHQUAKE SPECTRA, 2013, 29 (04) : 1353 - 1367