Particle-Triggered Corona Discharge Characteristics in Air Insulation Under DC Voltage

被引:12
作者
Fahmi, Daniar [1 ]
Illias, Hazlee Azil [1 ]
Mokhlis, Hazlie [1 ]
Negara, I. Made Yulistya [2 ]
机构
[1] Univ Malaya, Fac Engn, Dept Elect Engn, Kuala Lumpur 50603, Malaysia
[2] Sepuluh Nopember Inst Technol ITS, Dept Elect Engn, Surabaya 60111, Indonesia
关键词
Discharges (electric); Electrodes; Wires; Corona; Partial discharges; Particle measurements; Atmospheric measurements; Air insulation; corona discharge; metal contaminant; pulse sequence analysis (PSA); AC; BEHAVIOR; PERFORMANCE; MOVEMENT; GIS; SF6;
D O I
10.1109/TDEI.2022.3218519
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Under a dc stress, a wire particle within gas insulation will exhibit complex motion behavior, leading to more challenges to detect its existence. Therefore, this work deals with an investigation of corona discharge characteristics generated from a wire particle with different particle positions in an air gap. Three different wire particles are prepared in this investigation. The particle is placed between parallel-plane electrodes with a fixed gap of 20 mm. Five different positions are evaluated to study the partial discharge (PD) behavior generated from the wire particle. The exponential probability distribution is used to evaluate the pulse occurrences from different positions. Pulse sequence analysis (PSA) technique is employed, and an interpretation algorithm is introduced to understand the discharge pattern. The results show that each of the particle positions creates a unique pattern, which discharge mechanism behind the pattern is explained. From the pattern observation, a wire particle has single cluster of corona type as attached to the electrode while multiclusters are found when it is floating in the gap. Moreover, it is also found that different particle lengths are also affecting the discharge pattern characteristic.
引用
收藏
页码:658 / 666
页数:9
相关论文
共 25 条
[1]   Bipolar DC corona discharge from a floating filamentary metal-particle [J].
Asano, K ;
Hishinuma, R ;
Yatsuzuka, K .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (01) :57-63
[2]   DC corona discharge of a metal filament particle within parallel-plate electrodes [J].
Asano, K ;
Yatsuzuka, K ;
Yamaki, T .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2000, 36 (01) :87-92
[3]   INFLUENCE OF PARTICLES ON AC AND DC ELECTRICAL PERFORMANCE OF GAS INSULATED SYSTEMS AT EXTRA-HIGH-VOLTAGE [J].
COOKE, CM ;
WOOTTON, RE ;
COOKSON, AH .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (03) :768-777
[4]  
Dai F., 2020, PROC 12 IEEE PES ASI, P1, DOI [10.1109/APPEEC48164.2020.9220699, DOI 10.1109/APPEEC48164.2020.9220699]
[5]   Movement Behavior and Partial Discharge of the Single Metallic Particle in GIS at Operated Voltage [J].
Ge, Xiaoning ;
Ji, Hongxin ;
Cui, Xiwang ;
Li, Chengrong .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2019, 47 (09) :4319-4328
[6]   Particle-triggered pre-breakdown phenomena in atmospheric air gap under ac voltage [J].
Hara, M ;
Negara, Y ;
Setoguchi, M ;
Kurihara, T ;
Suehiro, J ;
Hayashi, N .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2005, 12 (05) :1071-1081
[7]   Moving Behaviors and Harmfulness Analysis of Multiple Linear Metal Particles in GIS [J].
Ji, Hong-xin ;
Li, Cheng-rong ;
Pang, Zhi-kai ;
Ma, Guo-ming ;
Cui, Xi-wang ;
Zeng, Zi-peng ;
Rong, Zhi-hai .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (06) :3355-3363
[8]   Partial Discharge Analysis and Simulation Using the Consecutive Pulses Correlation Method [J].
Kozak, Ondrej ;
Pihera, Josef .
ENERGIES, 2021, 14 (09)
[9]   DC corona discharge from a wire particle floated with a microgap in parallel plate electrodes [J].
Kudo, Yusuke ;
Sugimoto, Toshiyuki ;
Higashiyama, Yoshio .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2006, 42 (04) :909-915
[10]   Surface Charge Characteristics of DC-GIL Insulator Under Multiphysics Fields: 3-D Modeling [J].
Li, Xiaolong ;
Wan, Mingde ;
Zhang, Guangkuo ;
Lin, Xin .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (04) :1608-1616