Simulation and analysis of UHV half wavelength and DC hybrid transmission system

被引:3
|
作者
Qianyu Zhao [1 ]
Shouxiang Wang [1 ]
Xiaohui Qin [2 ]
Seyedamirabbas Mousavian [3 ]
Lei Wu [4 ]
机构
[1] Tianjin University, Key Laboratory of Smart Grid of Ministry of Education
[2] China Electric Power Research Institute
[3] School of Business, Clarkson University
[4] Department of Electrical and Computer Engineering, Clarkson University
关键词
UHV half-wavelength AC power transmission line; UHV DC system; Steady state characters; Transient stability;
D O I
10.14171/j.2096-5117.gei.2018.03.008
中图分类号
TM721.1 [直流制输电];
学科分类号
摘要
The scenarios of a half wavelength transmission line(HWTL) connected to the original DC asynchronous interconnection system are established based on the quasi-steady state model of HWTL, which include single or double loops of single channel and multi-channel scenarios with different starting and landing points. Firstly, the steady state power flow characters of multi-scenario transmission schemes are studied. The voltage distribution characters of HWTL are analyzed when its transmission power and power factor vary, and the influence of the DC power variation on voltage of HWTL is discussed. Then the transient characters of HWDHTS are explored. The DC commutation failure caused by the fault of HWTL is simulated and the power transfer capacity of HWTL while DC blocking is calculated in this paper.
引用
收藏
页码:366 / 375
页数:10
相关论文
共 50 条
  • [1] DC Commutation Failure Analysis for the Sending-Side System Fault in Hybrid UHV Half-Wavelength and UHV DC Transmission System
    Zhao, Qianyu
    Jiang, Yilang
    Wang, Shouxiang
    Qin, Xiaohui
    Mu, Hao
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2023, 51 (04) : 319 - 331
  • [2] Research on UHV Half Wavelength Ac Transmission Technology
    Peng, Qian
    Hou, Zhongwei
    Wang, Ye
    2015 4TH INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENTAL PROTECTION (ICEEP 2015), 2015, : 203 - 210
  • [3] Simulation Study of overvoltage in UHV AC and DC Hybrid System
    Li, Hongwei
    Peng, Ganrong
    2015 IEEE ADVANCED INFORMATION TECHNOLOGY, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (IAEAC), 2015, : 1215 - 1219
  • [4] Economic analysis and reliability assessment of UHV half-wavelength AC transmission
    Song, Yunting
    Zhou, Xiao
    Li, Bihui
    Zhang, Zhiqiang
    Zhang, Dongxia
    Qin, Xiaohui
    Lin, Jiming
    Han, Bin
    Dianwang Jishu/Power System Technology, 2011, 35 (09): : 1 - 6
  • [5] Adaptability Analysis of Differential Protection for UHV Half-wavelength AC Transmission Line
    Ma, Xiaowei
    Zhang, Ming
    Gao, Jiaxiong
    Wang, Qingping
    Bo, Zhiqian
    Zhao, Yingke
    Zhu, Yi
    Zheng, Hao
    2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [6] Research on fault location for UHV half-wavelength transmission lines
    Wang, Guan
    Zhao, Haoran
    Hao, Qingshui
    China International Conference on Electricity Distribution, CICED, 2018, : 1341 - 1345
  • [7] Research on Fault Location for UHV Half-wavelength Transmission Lines
    Wang, Guan
    Zhao, Haoran
    Hao, Qingshui
    2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 1341 - 1345
  • [8] Insulation coordination of UHV half-wavelength AC transmission line
    Peng, Qian
    Li, Shifeng
    Dianwang Jishu/Power System Technology, 2014, 38 (04): : 1082 - 1086
  • [9] Digital simulation of AC/DC hybrid transmission system
    Yong, J
    Wu, XC
    Du, ZM
    Jin, XM
    Wang, YH
    Zhang, DH
    Rittiger, J
    POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 1405 - 1410
  • [10] Characteristics of Transient Recovery Voltage of Circuit Breakers in UHV AC Half-wavelength Transmission System
    Wang P.
    Han B.
    Zhang Y.
    Xiang Z.
    Ban L.