Development of a control system for the fourth-harmonic cavity of the HLS storage ring

被引:0
作者
Wen-Bo Wu [1 ]
Ke Xuan [1 ]
Wei Xu [1 ]
Ji-Gang Wang [1 ]
Chuan Li [1 ]
Gong-Fa Liu [1 ]
Cong-Feng Wu [1 ]
Jing-Yi Li [1 ,2 ]
机构
[1] National Synchrotron Radiation Laboratory,University of Science and Technology of China
[2] Institute of High Energy Physics,CAS
基金
中国国家自然科学基金;
关键词
Bunch length; High-harmonic cavity; EPICS; PID feedback;
D O I
暂无
中图分类号
TL594 [储存环(对头碰)];
学科分类号
082701 ;
摘要
Harmonic RF cavities are commonly used in storage rings to lengthen the bunches and thus suppress the beam’s instabilities and increase its Touschek lifetime. The voltage and phase of the electromagnetic fields in the harmonic cavity are of great importance for stretching the bunch. In the Hefei Light Source storage ring, a passive fourth-harmonic cavity is installed, and the cavity is monitored and controlled by an analog control module provided by its manufacturer. To vary and maintain the voltage of the harmonic cavity in a more effective way, a digital proportional, integral, and derivative feedback system based on the Experimental Physics and Industrial Control System is developed on top of the analog control module. This paper reports the details of the development of this voltage control system. Some test and operational results are also presented.
引用
收藏
页码:69 / 75
页数:7
相关论文
共 6 条
[1]   Design of a higher harmonic cavity for the SSRF storage ring [J].
马广明 ;
赵振堂 ;
刘建飞 .
中国物理C, 2008, (04) :275-279
[2]  
The Sirius project[J] . Lin Liu,Natalia Milas,Afonso H. C. Mukai,Ximenes R. Resende,Fernando H. de Sá.Jnl of Synchrotron Radiation . 2014 (5)
[3]   Calculations of operating schemes for a passive harmonic cavity in HLS-II [J].
Fan Hao ;
Wu Cong-Feng ;
Liu Guang-Chao .
CHINESE PHYSICS C, 2012, 36 (09) :895-899
[4]   Commissioning of a higher harmonic RF system for the Advanced Light Source [J].
Byrd, JM ;
De Santis, S ;
Georgsson, M ;
Stover, G ;
Fox, JD ;
Teytelman, D .
NUCLEAR INSTRUMENTS & METHODS IN PHYSICS RESEARCH SECTION A-ACCELERATORS SPECTROMETERS DETECTORS AND ASSOCIATED EQUIPMENT, 2000, 455 (02) :271-282
[5]  
P.F.Tavares,S.C.Leemann,M.Sjo¨stro¨m. J.Synchrotron Radiat . 2014
[6]  
Commissioning of the harmonic cavities in the MAX IV 3 GeV ring .2 G.Skripka,Andersson,A.Mitrovic.et al. Proceedings of IPAC2016 . 2016