Open-circuit fault diagnosis and fault tolerance for shunt active power filter

被引:0
|
作者
彭涛 [1 ]
赵帅 [1 ]
但汉兵 [1 ]
玉华雄 [1 ]
机构
[1] School of Information Science and Engineering,Central South University
关键词
fault diagnosis; fault tolerant; reference model; over-modulation; three-phase four-switch topology; shunt active power filter;
D O I
暂无
中图分类号
TM761 [自动调整];
学科分类号
080802 ;
摘要
The open-circuit fault of the power switches in shunt active power filter(SAPF) would exacerbate the harmonic pollution of power grid, and degrade the reliability of the devices and system. A fault diagnosis method is proposed based on reference model and an over-modulation strategy under hardware fault tolerance for SAPF. First, a mathematic model is established for SAPF. Second, the residuals are generated by comparing the outputs of reference model and those of actual model, and open-switch fault is detected and diagnosed by residual evaluation. After that, hardware fault tolerance is performed with the three-phase four-switch(TPFS) topology to isolate the faulty phase. Finally, the over-modulation strategy is proposed to increase the voltage transfer ratio of the TPFS topology. Simulation and experimental results verified the feasibility and effectiveness of the proposed method.
引用
收藏
页码:2582 / 2595
页数:14
相关论文
共 50 条
  • [1] Open-circuit fault diagnosis and fault tolerance for shunt active power filter
    Peng Tao
    Zhao Shuai
    Dan Han-bing
    Yu Hua-xiong
    JOURNAL OF CENTRAL SOUTH UNIVERSITY, 2017, 24 (11) : 2582 - 2595
  • [2] Open-circuit fault diagnosis and fault tolerance for shunt active power filter
    Tao Peng
    Shuai Zhao
    Han-bing Dan
    Hua-xiong Yu
    Journal of Central South University, 2017, 24 : 2582 - 2595
  • [3] Fault Diagnosis for shunt hybrid Active Power Filter with Open-circuit Fault Based on Voltage Distortion
    Peng, Tao
    Zhao, Shuai
    Lin, Zhili
    Sun, Yao
    Mao, Yongmei
    2015 CHINESE AUTOMATION CONGRESS (CAC), 2015, : 2163 - 2168
  • [4] Open-Circuit Fault Diagnosis in Shunt Active Power Filters with No Additional Sensors
    Liu, Yujia
    Han, Pengcheng
    He, Xiaoqiong
    Shu, Zeliang
    Gao, Shibin
    PROCEEDINGS OF THE 15TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2020), 2020, : 1389 - 1394
  • [5] An Open-Circuit Fault Detection Based on Model Reference for Active Power Filter
    Yu Huaxiong
    Peng Tao
    Han Hua
    Lin Zhili
    Zhang Wei
    2014 33RD CHINESE CONTROL CONFERENCE (CCC), 2014, : 3323 - 3327
  • [6] Research of open-circuit fault simulation and diagnosis for wind power converter
    Zhang, Wei
    Ling, Qihui
    Zhao, Qiancheng
    Wang, Xian
    Zeng, Bing
    NINTH INTERNATIONAL SYMPOSIUM ON PRECISION MECHANICAL MEASUREMENTS, 2019, 11343
  • [7] Fault Diagnosis and Tolerance for Open-circuit Faults in Multi-Level Inverters
    Halabi, Laith M.
    Alsofyani, Ibrahim Mohd
    Lee, Kyo-Beum
    2022 INTERNATIONAL POWER ELECTRONICS CONFERENCE (IPEC-HIMEJI 2022- ECCE ASIA), 2022, : 849 - 853
  • [8] An Open-Circuit Fault Diagnosis Method for LLC Converters
    Xiong, Shibo
    Pei, Yuxuan
    Wang, Weikang
    Liu, Wenwei
    Zhang, Peng
    Liu, Yang
    ENERGIES, 2024, 17 (04)
  • [9] A fault tolerance method based on switch redundancy for shunt active power filter
    Chen, Dongdong
    Xiao, Long
    Lian, Hemiu
    Xu, Zhenming
    ENERGY REPORTS, 2021, 7 : 449 - 457
  • [10] Open-Circuit Fault Detection and Diagnosis in Matrix Converters
    Brunson, Christopher
    Empringham, Lee
    De Lillo, Liliana
    Wheeler, Patrick
    Clare, Jon
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (05) : 2840 - 2847