Developing a chloramine decay index to understand nitrification:A case study of two chloraminated drinking water distribution systems

被引:1
|
作者
Sina Moradi [1 ]
Sanly Liu [1 ]
Christopher W.K.Chow [2 ,3 ]
John van Leeuwen [3 ]
David Cook [2 ]
Mary Drikas [2 ]
Rose Amal [1 ]
机构
[1] School of Chemical Engineering,The University of New South Wales
[2] Australian Water Quality Centre,SA Water Corporation
[3] Centre for Water Management and Reuse,School of Natural and Built Environments,University of South Australia
基金
澳大利亚研究理事会;
关键词
HPSEC; Water distribution systems; Nitrification; Chloramine decay;
D O I
暂无
中图分类号
TU991.25 [饮水消毒、水生物防除];
学科分类号
0815 ;
摘要
The management of chloramine decay and the prevention of nitrification are some of the critical issues faced by water utilities that use chloramine as a disinfectant.In this study,potential association between high performance size exclusion chromatography(HPSEC)data obtained with multiple wavelength Ultraviolet(UV) detection from two drinking water distribution systems in Australia and nitrification occurrence was investigated.An increase in the absorbance signal of HPSEC profiles with UV detection at λ = 230 nm between apparent molecular weights of 200 to 1000 Da was observed at sampling sites that experienced rapid chloramine decay and nitrification while its absorbance signal at λ =254 nm decreased.A chloramine decay index(C.D.I) defined as the ratio of area beneath the HPSEC spectra at two different wavelengths of 230 and 254 nm,was used in assessing chloramine decay occurrences.The C.D.Is of waters at locations that experienced nitrification were consistently higher than locations not experiencing nitrification.A simulated laboratory study showed that the formation of nitrite/nitrate and/or soluble microbial products and/or the release of extracellular polymeric substances(EPS) during nitrification may contribute to the C.D.I.increase.These findings suggest that C.D.I derived from HPSEC with multiple wavelength UV detection could be an informative index to track the occurrence of rapid chloramine decay and nitrification.
引用
收藏
页码:170 / 179
页数:10
相关论文
共 16 条
  • [1] Developing a chloramine decay index to understand nitrification: A case study of two chloraminated drinking water distribution systems
    Moradi, Sina
    Liu, Sanly
    Chow, Christopher W. K.
    van Leeuwen, John
    Cooke, David
    Drikas, Mary
    Amal, Rose
    JOURNAL OF ENVIRONMENTAL SCIENCES, 2017, 57 : 170 - 179
  • [2] Estimation of chloramine decay in drinking water distribution systems
    Curling, Emily A.
    McKie, Michael J.
    Meteer, Laura
    Saunders, Blair
    Andrews, Susan A.
    Andrews, Robert C.
    JOURNAL OF WATER PROCESS ENGINEERING, 2022, 46
  • [3] Monitoring of Nitrification in Chloraminated Drinking Water Distribution Systems With Microbiome Bioindicators Using Supervised Machine Learning
    Gomez-Alvarez, Vicente
    Revetta, Randy P.
    FRONTIERS IN MICROBIOLOGY, 2020, 11
  • [4] Modeling chloramine decay in full-scale drinking water supply systems
    Ricca, Henry
    Aravinthan, Vasanthadevi
    Mahinthakumar, Gnanamanikam
    WATER ENVIRONMENT RESEARCH, 2019, 91 (05) : 441 - 454
  • [5] Treatment and distribution system effects on chloramine decay, pH, nitrification, and disinfection by-products: Case study
    Sung, WD
    Huang, X
    Wei, IW
    JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT, 2005, 131 (03) : 201 - 207
  • [6] Simplified chemical chloramine decay model for water distribution systems
    Roy, Reyad
    Sathasivan, Arumugam
    Kastl, George
    SCIENCE OF THE TOTAL ENVIRONMENT, 2020, 741
  • [7] Characters of chloramine decay in large looped water distribution system - the case of Tianjin, China
    Ma, Kai
    Hu, Jiankun
    Han, Hongda
    Zhao, Lin
    Li, Rong
    Su, Xiao
    WATER SUPPLY, 2020, 20 (04) : 1474 - 1483
  • [8] Occurrence of nitrifying bacteria and nitrification in Finnish drinking water distribution systems
    Lipponen, MTT
    Suutari, MH
    Martikainen, PJ
    WATER RESEARCH, 2002, 36 (17) : 4319 - 4329
  • [9] Using nitrification potential curves to evaluate full-scale drinking water distribution systems
    American Water, 1025 Laurel Oak Rd., Voorhees, NJ 08043, United States
    不详
    J Am Water Works Assoc, 2008, 10 (92-103+10):
  • [10] Influence of water quality on nitrifier regrowth in two full-scale drinking water distribution systems
    Scott, Daniel B.
    Van Dyke, Michele I.
    Anderson, William B.
    Huck, Peter M.
    CANADIAN JOURNAL OF MICROBIOLOGY, 2015, 61 (12) : 965 - 976