Hydroxyl carboxylate based non-phosphorus corrosion inhibition process for reclaimed water pipeline and downstream recirculating cooling water system

被引:5
|
作者
Jun Wang [1 ,2 ]
Dong Wang [1 ,3 ]
Deyin Hou [1 ,2 ]
机构
[1] Key Laboratory of Drinking Water Science and Technology, Research Center for Eco-Environmental Sciences, Chinese Academy of Sciences
[2] Yanshan Branch, SINOPEC Beijing Research Institute of Chemical Industry
[3] Beijing Key Laboratory of Industrial Wastewater Treatment and Reuse, Research Center for Eco-Environmental Sciences, Chinese Academy of Sciences
基金
中国国家自然科学基金;
关键词
Hydroxyl carboxylate; Reclaimed water; Pipeline; Corrosion; Recirculating cooling water system; Non-phosphorus;
D O I
暂无
中图分类号
TU991.57 [中水道给水]; TU991.4 [工业企业给水];
学科分类号
0815 ;
摘要
A combined process was developed to inhibit the corrosion both in the pipeline of reclaimed water supplies(PRWS) and in downstream recirculating cooling water systems(RCWS)using the reclaimed water as makeup. Hydroxyl carboxylate-based corrosion inhibitors(e.g.,gluconate, citrate, tartrate) and zinc sulfate heptahydrate, which provided Znas a synergistic corrosion inhibition additive, were added prior to the PRWS when the phosphate(which could be utilized as a corrosion inhibitor) content in the reclaimed water was below 1.7 mg/L, and no additional corrosion inhibitors were required for the downstream RCWS.Satisfactory corrosion inhibition was achieved even if the RCWS was operated under the condition of high numbers of concentration cycles. The corrosion inhibition requirement was also met by the appropriate combination of POand Znwhen the phosphate content in the reclaimed water was more than 1.7 mg/L. The process integrated not only water reclamation and reuse, and the operation of a highly concentrated RCWS, but also the comprehensive utilization of phosphate in reclaimed water and the application of non-phosphorus corrosion inhibitors. The proposed process reduced the operating cost of the PRWS and the RCWS, and lowered the environmental hazard caused by the excessive discharge of phosphate. Furthermore, larger amounts of water resources could be conserved as a result.
引用
收藏
页码:13 / 21
页数:9
相关论文
共 44 条
  • [1] Hydroxyl carboxylate based non-phosphorus corrosion inhibition process for reclaimed water pipeline and downstream recirculating cooling water system
    Wang, Jun
    Wang, Dong
    Hou, Deyin
    JOURNAL OF ENVIRONMENTAL SCIENCES, 2016, 39 : 13 - 21
  • [2] CORROSION AND SCALE INHIBITION IN RECIRCULATING COOLING WATER SYSTEM BY LOW CONCENTRATION OF INORGANIC AND ORGANIC INHIBITORS.
    Kurmaiah, N.
    Saha, G.
    Transactions of the SAEST (Society for Advancement of Electrochemical Science and Technology), 1984, 19 (02): : 173 - 176
  • [3] Corrosion and scale inhibition properties of sodium lignosulfonate and its potential application in recirculating cooling water system
    Ouyang, Xinping
    Qiu, Xueqing
    Lou, Hongming
    Yang, Dongjie
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2006, 45 (16) : 5716 - 5721
  • [4] A synergistic effect between gluconate and molybdate on corrosion inhibition of recirculating cooling water systems
    Ou, Hsin-Hung
    Quynh Thi Phuong Tran
    Lin, Po-Hsun
    CORROSION SCIENCE, 2018, 133 : 231 - 239
  • [5] A non-phosphorus water treatment agent in water injection system: inhibiting strontium sulfate and dispersing ferric oxide
    Liu, Y. M.
    Zhou, Y. M.
    Yao, Q. Z.
    Wu, Z.
    Chen, Y. Y.
    She, C. G.
    Wu, W. D.
    Sun, W.
    WATER SCIENCE AND TECHNOLOGY-WATER SUPPLY, 2017, 17 (02): : 352 - 361
  • [6] CORROSION INHIBITION OF MOLYBDATE AND NITRITE FOR CARBON STEEL CORROSION IN PROCESS COOLING WATER
    Yee, J. C.
    Kee, K. E.
    Hassan, Suhaimi
    Nor, M. Faizairi M.
    Ismail, M. C.
    JOURNAL OF ENGINEERING SCIENCE AND TECHNOLOGY, 2019, 14 (04): : 2431 - 2444
  • [7] Inhibition Effect of Environment-Friendly Inhibitors on the Corrosion of Carbon Steel in Recirculating Cooling Water
    He, Chengjun
    Tian, Zhipeng
    Zhang, Bingru
    Lin, Yu
    Chen, Xi
    Wang, Meijing
    Li, Fengting
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2015, 54 (07) : 1971 - 1981
  • [8] FOULING AND CORROSION IN OPEN, RECIRCULATING COOLING WATER-SYSTEMS - THE EXPERT SYSTEM APPROACH
    FELTZIN, AE
    GARCIA, H
    LACAVA, AI
    MATERIALS PERFORMANCE, 1988, 27 (06) : 57 - 61
  • [9] A green corrosion inhibitor for soft, low-alkalinity water in a recirculating cooling system
    Zhou, Baiqing
    Liu, Xia
    Xu, Shujiao
    MATERIALS PERFORMANCE, 2008, 47 (09) : 50 - 54
  • [10] Effect of phosphonate based corrosion inhibitors in a cooling water system
    Mosayebi, B
    Kazemeini, M
    Badakhshan, A
    BRITISH CORROSION JOURNAL, 2002, 37 (03): : 217 - 224