Voltage Characteristic Analysis of Ultra-high Voltage Half-wavelength Transmission System Based on Wave Process Method

被引:0
|
作者
Hao Tian [1 ]
Yutian Liu [1 ]
Dong Yang [2 ]
Xiaohui Qin [3 ]
Yantao Zhang [3 ]
机构
[1] Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education, Shandong University
[2] State Grid Shandong Electric Power Research Institute
[3] China Electric Power Research Institute
关键词
Half-wavelength transmission; wave process method; steady-state voltage; fault voltage; non-ideal factor;
D O I
暂无
中图分类号
TM714.2 [电压调整];
学科分类号
080802 ;
摘要
The voltage characteristics of a half-wavelength transmission(HWLT) system lack mechanism explanation and systematic summary. In this paper, both the steady-state and fault voltage characteristics are analyzed and explained based on the wave process method. An analysis model is established for HWLT lines and wave propagation equations with different terminal conditions are deduced. For steady-state conditions,voltage profiles along HWLT lines are depicted and partial overvoltage occurs when there is an overload or low-power factor.In addition, fault voltage characteristics are analyzed under load-rejection or short-circuit conditions. The series resonance overvoltage will happen when short-circuit faults occur at certain positions and its peak value is influenced by grid strength or fault type. Furthermore, a refined transmission line model is presented to consider non-ideal factors and simulation results demonstrate that geomorphic conditions and electromagnetic environments influence line voltage characteristics to a certain extent.
引用
收藏
页码:150 / 158
页数:9
相关论文
共 50 条
  • [1] Voltage Characteristic Analysis of Ultra-high Voltage Half-wavelength Transmission System Based on Wave Process Method
    Tian, Hao
    Liu, Yutian
    Yang, Dong
    Qin, Xiaohui
    Nang, Yantao
    JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2020, 8 (01) : 150 - 158
  • [2] Aspects of ultra-high voltage half-wavelength power transmission technology
    Yutian Liu
    Hao Tian
    Zhengzhong Liu
    Xiaohui Qin
    Global Energy Interconnection, 2018, 1 (01) : 96 - 102
  • [3] An improved secondary voltage control method for half-wavelength transmission system
    Tian, Hao
    Liu, Yutian
    Zhang, Yantao
    Qin, Xiaohui
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 115
  • [4] Steady state voltage characteristic of UHV half-wavelength AC transmission line
    Zhang, Zhiqiang
    Qin, Xiaohui
    Wang, Haohuai
    Xu, Zhengxiong
    Zhang, Dongxia
    Lin, Jiming
    Zheng, Jianchao
    Dianwang Jishu/Power System Technology, 2011, 35 (09): : 33 - 36
  • [5] Reactive Power Optimization and Voltage Control for Half-Wavelength Power Transmission System
    Tian, Hao
    Liu, Yutian
    Yang, Dong
    Qin, Xiaohui
    TENCON 2017 - 2017 IEEE REGION 10 CONFERENCE, 2017, : 1931 - 1935
  • [6] Characteristics of Transient Recovery Voltage of Circuit Breakers in UHV AC Half-wavelength Transmission System
    Wang P.
    Han B.
    Zhang Y.
    Xiang Z.
    Ban L.
    Gaodianya Jishu/High Voltage Engineering, 2018, 44 (01): : 22 - 28
  • [7] Transmission characteristic and reactive power compensation of ultra-high voltage AC transmission line
    Cheng, Tao
    Lin, Li
    Mou, Dao-Huai
    Sun, Cai-Xin
    Chongqing Daxue Xuebao/Journal of Chongqing University, 2010, 33 (01): : 83 - 87
  • [8] Transient Stability Analysis of Half-wavelength Transmission System
    Li, Junjie
    Wang, Guan
    Su, Xiaomeng
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 392 - 397
  • [9] Seismic performance analysis of ultra-high voltage transmission tower-line system based on capacity spectrum method
    Wang, Wenming
    Sheng, Hanke
    Gao, Yahui
    Zhang, Shibo
    STRUCTURES, 2024, 61
  • [10] High-frequency Half-wavelength Transmission System and Its Economic Analysis
    Xie Q.
    Wang Y.
    Xiao X.
    Dianwang Jishu/Power System Technology, 2020, 44 (07): : 2610 - 2616