Modeling and Experimental Investigation of a Variable Speed Drive Water Source Heat Pump

被引:4
作者
薛志方 [1 ,2 ]
史琳 [1 ]
机构
[1] Key Laboratory for Thermal Science and Power Engineering of Ministry of Education, Department of Thermal Engineering, Tsinghua University
[2] Guangxi Electric Power Industry Investigation Design and Research Institute
基金
中国国家自然科学基金;
关键词
scroll compressor; variable speed control; modeling; frequency conversion; water source heat pump;
D O I
暂无
中图分类号
TH38 [各种用途];
学科分类号
080704 ;
摘要
Accurate variable speed characteristics are needed for water source heat pumps (WSHP) to design variable speed controls to adjust refrigerant flow rates in heat pumps and air conditioners. The system capacity can then be regulated to match the compressor loads to the heating or cooling needs to improve the energy efficiency and lower energy costs. The motor and compression characteristics of WSHP were modeled to include the coupling between the motor speed and the torque characteristics and compression characteristics. An analytical model is given for a variable speed hermetic scroll compressor that describes various factors, such as the drive frequency, suction pressure, and discharge pressure as a function of the compressor speed. The model was validated experimentally using R22 and R134a in an experimental WSHP with variable speed control using frequency conversion. The results show that the analytical model properly describes the variable speed characteristics and provides a control strategy for adjusting the capacity of scroll compressors to match the heat pump or air conditioner operating conditions.
引用
收藏
页码:434 / 440
页数:7
相关论文
共 8 条
  • [1] Fuzzy control of the compressor speed in a refrigeration plant
    Aprea, C
    Mastrullo, R
    Renno, C
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (06): : 639 - 648
  • [2] Performance representation of variable-speed compressor for inverter air conditioners based on experimental data
    Shao, SQ
    Shi, WX
    Li, XT
    Chen, HJ
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (08): : 805 - 815
  • [3] Refrigeration plant exergetic analysis varying the compressor capacity
    Aprea, C
    de Rossi, F
    Greco, A
    Renno, C
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2003, 27 (07) : 653 - 669
  • [4] Thermodynamic analysis on the performance of a variable speed scroll compressor with refrigerant injection
    Park, YC
    Kim, Y
    Cho, H
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (08): : 1072 - 1082
  • [5] Experimental study on the performance of an inverter heat pump with a bypass orifice
    Choi, J
    Kim, Y
    Kim, J
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (05): : 417 - 427
  • [6] Performance analysis on a multi-type inverter air conditioner
    Park, YC
    Kim, YC
    Min, MK
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2001, 42 (13) : 1607 - 1621
  • [7] Comparative performance evaluation of positive displacement compressors in variable-speed refrigeration applications
    Tassou, SA
    Qureshi, TQ
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (01): : 29 - 41
  • [8] Variable-speed capacity control in refrigeration systems
    Qureshi, TQ
    Tassou, SA
    [J]. APPLIED THERMAL ENGINEERING, 1996, 16 (02) : 103 - 113