Stability of LCL-filtered grid-connected inverters with capacitor current feedback active damping considering controller time delays

被引:0
|
作者
Wei XIA [1 ]
Jinsong KANG [1 ]
机构
[1] School of Electronics and Information Engineering, Tongji University
关键词
LCL filter; Grid-connected inverter; Controller time delays; Stability;
D O I
暂无
中图分类号
TM53 [电容器]; TM464 [逆变器];
学科分类号
摘要
This paper investigates the stability of LCL-filtered grid-connected inverters with capacitor current feedback(CCF) active damping. The impact of time delays in the digital controller on active damping and its equivalent virtual impedance is analyzed. The inherent relationship between these time delays and stability is illustrated.Specially, a critical value of the CCF active damping coefficient kdamp;is proposed to define three distinct regions of stability evaluation. If kdamp;[ 0, a sufficient but smaller damping coefficient(kdamp kdamp;) is recommended as optimum damping solution; if kdamp;= 0,system will be unstable irrespective of active damping; and if kdamp;\ 0, active damping is not necessary to design a stable system. Necessary conditions to ensure stability are identified; guidelines for controller design are then presented to optimize the performance of active damping and dynamic response. Simulation and experimental results confirm the presented analysis.
引用
收藏
页码:584 / 598
页数:15
相关论文
共 50 条
  • [41] Stability Analysis and Improvement of the Capacitor Current Active Damping of the LCL Filters in Grid-Connected Applications
    Xu, Jinming
    Xie, Shaojun
    Zhang, Binfeng
    JOURNAL OF POWER ELECTRONICS, 2016, 16 (04) : 1565 - 1577
  • [42] Observer-based Control for Grid-connected LCL-filtered Inverter with Only Grid Current Feedback
    Lai, Ngoc-Bao
    Kim, Kyeong-Hwa
    2ND INTERNATIONAL CONFERENCE ON APPLIED MECHANICS, ELECTRONICS AND MECHATRONICS ENGINEERING (AMEME), 2017, : 167 - 170
  • [43] Highly Accurate Digital Current Controllers for Single-Phase LCL-Filtered Grid-Connected Inverters
    Busarello, Tiago Davi Curi
    Zeb, Kamran
    Simoes, Marcelo Godoy
    ELECTRICITY, 2020, 1 (01): : 12 - 36
  • [44] Robust Capacitor-Current-Feedback Active Damping for the LCL-Type Grid-Connected Inverter
    Pan, Donghua
    Ruan, Xinbo
    Wang, Xuehua
    Bao, Chenlei
    Li, Weiwei
    2013 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2013, : 728 - 735
  • [45] Synthesis of Active Damping for Grid-Connected Inverters with an LCL filter
    Xiao, Huafeng
    Qu, Xiaohui
    Xie, Shaojun
    Xu, Jinming
    2012 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2012, : 550 - 556
  • [46] Design of IDA-PBC Controller for LCL-Filtered Grid-Connected Inverter
    Huang, Min
    Chen, Fan
    Zhang, Zhicheng
    Wu, Weimin
    Yao, Zhilei
    Zhu, Lixun
    IECON 2021 - 47TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2021,
  • [47] Capacitive Emulation for LCL-Filtered Grid-Connected Converters
    Miguel Espi, Jose
    Garcia-Gil, Rafael
    Castello, Jaime
    ENERGIES, 2017, 10 (07):
  • [48] Current Control of LCL-Filtered Grid-Connected VSC using Model Predictive Control with Inherent Damping
    Norgaard, Jacob Bitsch
    Graungaard, Mads Kjeldal
    Dragicevic, Tomislav
    Blaabjerg, Frede
    2018 20TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'18 ECCE EUROPE), 2018,
  • [49] Attenuation of Low-Order Current Harmonics in Three-Phase LCL-Filtered Grid-Connected Inverters
    Wang, Jianguo
    Yan, Jiu Dun
    Jiang, Lin
    Zou, Jiyan
    IECON 2015 - 41ST ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2015, : 1982 - 1987
  • [50] Design Considerations of Digitally Controlled LCL-Filtered Inverter With Capacitor-Current-Feedback Active Damping
    Wang, Xuehua
    Bao, Chenlei
    Ruan, Xinbo
    Li, Weiwei
    Pan, Donghua
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2014, 2 (04) : 972 - 984