Stability of LCL-filtered grid-connected inverters with capacitor current feedback active damping considering controller time delays

被引:0
作者
Wei XIA
Jinsong KANG
机构
[1] SchoolofElectronicsandInformationEngineering,TongjiUniversity
关键词
LCL filter; Grid-connected inverter; Controller time delays; Stability;
D O I
暂无
中图分类号
TM53 [电容器]; TM464 [逆变器];
学科分类号
080801 ;
摘要
This paper investigates the stability of LCL-filtered grid-connected inverters with capacitor current feedback(CCF) active damping. The impact of time delays in the digital controller on active damping and its equivalent virtual impedance is analyzed. The inherent relationship between these time delays and stability is illustrated.Specially, a critical value of the CCF active damping coefficient kdamp_cis proposed to define three distinct regions of stability evaluation. If kdamp_c[ 0, a sufficient but smaller damping coefficient(kdamp kdamp_c) is recommended as optimum damping solution; if kdamp_c= 0,system will be unstable irrespective of active damping; and if kdamp_c 0, active damping is not necessary to design a stable system. Necessary conditions to ensure stability are identified; guidelines for controller design are then presented to optimize the performance of active damping and dynamic response. Simulation and experimental results confirm the presented analysis.
引用
收藏
页码:584 / 598
页数:15
相关论文
共 1 条
[1]  
Overview of control, integration and energy management of microgrids[J] . Yunwei LI,Farzam NEJABATKHAH. Journal of Modern Power Systems and Clean Energy . 2014 (3)