首页
学术期刊
论文检测
AIGC检测
热点
更多
数据
Effects of non-condensable gases on heat transfer performance of loop thermosyphon for CPU cooling
被引:0
作者
:
Toyoda, Hiroyuki
论文数:
0
引用数:
0
h-index:
0
机构:
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Toyoda, Hiroyuki
[
1
]
Kondo, Yoshihiro
论文数:
0
引用数:
0
h-index:
0
机构:
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Kondo, Yoshihiro
[
1
]
Sato, Shigemasa
论文数:
0
引用数:
0
h-index:
0
机构:
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Sato, Shigemasa
[
1
]
Tsubaki, Shigeyasu
论文数:
0
引用数:
0
h-index:
0
机构:
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
Tsubaki, Shigeyasu
[
1
]
机构
:
[1]
Hitachi Research Laboratory, Hitachi, Ltd., Horiguchi 832-1, Hitachinaka-shi, Ibaraki, 312-0034, Japan
来源
:
Nihon Kikai Gakkai Ronbunshu, B Hen/Transactions of the Japan Society of Mechanical Engineers, Part B
|
2012年
/ 78卷
/ 795期
关键词
:
Electronic cooling - Capillary flow - Siphons - Heat resistance - Technology transfer;
D O I
:
10.1299/kikaib.78.2030
中图分类号
:
学科分类号
:
摘要
:
We have developed a loop thermosyphon for cooling electronics devices. Non-condensable gases (NCG) in a loop thermosyphon increase by leakage from outside, release of the gas dissolved in the refrigerant, and chemical reaction in the inside. Hence, it is necessary to know how the heat transfer performance changes when the amount of NCG in a loop thermosyphon increases. The effect of NCG's amount was measured for each component of the loop thermosyphon while changing the amount of heat input. The overall thermal resistance of a loop thermosyphon increased with the amount of NCG The thermal resistance of the condensing part particularly increased with the NCG The effect of NCG on the boiling part should be considered only by steam temperature which was raised by increase in the amount of NCG. The thermal resistance of the air cooling part is not affected by NCG but the temperature difference of the air cooling part becomes smaller because heat-leakage increases with steam temperature. © 2012 The Japan Society of Mechanical Engineers.
引用
收藏
页码:2030 / 2045
相关论文
未找到相关数据
未找到相关数据