Adaptability Analysis of Half Wavelength Transmission Line Protection with Tuned Circuit

被引:0
作者
Han, Yiming [1 ]
Shu, Hongchun [1 ]
Fan, Zuoyun [1 ]
Cao, Pulin [1 ]
Tang, Yutao [1 ]
机构
[1] Faculty of Electric Power Engineering, Kunming University of Science and Technology, Kunming,650051, China
来源
Diangong Jishu Xuebao/Transactions of China Electrotechnical Society | 2020年 / 35卷
关键词
UHV power transmission - Tuning - Electric power system protection - Relay protection - Timing circuits;
D O I
10.19595/j.cnki.1000-6753.tces.191534
中图分类号
学科分类号
摘要
The actual transmission distance of UHV half-wavelength transmission lines is difficult to meet the conditions of half-wavelength, or even far less than half wavelength. Therefore, tuned half-wavelength transmission lines will become the main realization form of half wavelength AC transmission. In this paper, the PSCAD/EMTDC simulation model is used to analyze three main relay protection schemes for UHV AC transmission: current differential protection, distance protection and directional elements. At the same time, the difference of signal before and after the tuning device is analyzed. The results show that the tuning device will affect the amplitude of electrical quantity and cause phase deviation, except directional protection, current differential protection and distance protection are not suitable for transmission lines with tuned half-wavelength. © 2020, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:577 / 584
相关论文
empty
未找到相关数据