Enhancing Transient and Steady-State Performance in Grid-Connected VSCs: A Comprehensive Frequency Region Analysis of Decoupling Current Units

被引:0
作者
Forouzanfar, Mehdi [1 ]
Pinnarelli, Anna [1 ]
Mohammad Sadegh Ghiasi, Seyyed [1 ]
Menniti, Daniele [1 ]
Sorrentino, Nicola [1 ]
Brusco, Giovanni [1 ]
Vizza, Pasquale [1 ]
Safaiepour, Hossein [1 ]
机构
[1] Univ Calabria, Dept Mech Energy & Management Engn DIMEG, Arcavacata Di Rende, Rende, Italy
关键词
Mathematical models; Transient analysis; Steady-state; Power conversion; Integrated circuit modeling; Robustness; Voltage control; Power harmonic filters; Couplings; Tracking loops; Decoupling current control; LCL filter; RGA; robustness; steady-state; THD; transient; voltage source converter; DAMPING CONTROL; DESIGN; SYSTEM;
D O I
10.1109/ACCESS.2025.3588464
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper introduces an innovative synthesis of inner loop control for grid-connected Voltage Source Converters (VSCs), comprising a Decoupling Current Unit (DCU) with a classic current tracking controller. The objective is to enhance both transient and steady-state performance by reducing the inherent coupling between the d- and q-axis current control loops. The proposed DCU is formulated through a generalized control design approach that can be configured according to the dynamics of practical filter types, including L, LC, and LCL structures. Decoupling effectiveness is assessed through a model-independent Relative Gain Array (RGA) analysis, while the robustness of the inner control loop under parameter uncertainties is evaluated to ensure reliable steady-state performance. Theoretical analysis confirms that the proposed DCU effectively suppresses inter-axis coupling, producing RGA profiles that closely align with ideal decoupling across different filter configurations. These findings are further validated through simulation studies under both linear and nonlinear load conditions. Compared to a classic non-decoupled control scheme, the proposed method achieves substantial improvements: approximately 55% reduction in overshoot, up to 70% suppression of cross-coupling effects following power step changes, more than 60% improvement in reactive power tracking accuracy.
引用
收藏
页码:123682 / 123698
页数:17
相关论文
共 43 条
[1]  
Abolmasoumi AH, 2024, Arxiv, DOI arXiv:2406.13374
[2]   Dynamic modelling and interaction analysis of multi-terminal VSC-HVDC grids through an impedance-based approach [J].
Agbemuko, Adedotun J. ;
Luis Dominguez-Garcia, Jose ;
Prieto-Araujo, Eduardo ;
Gomis-Bellmunt, Oriol .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 113 :874-887
[3]  
Aijaz M., 2024, P 3 INT C INT TECHN, P1, DOI [10.1109/INCOS59338.2024.10527574, DOI 10.1109/INCOS59338.2024.10527574]
[4]   Power System Stability With High Penetration of Renewable Energy Sources: Challenges, Assessment, and Mitigation Strategies [J].
Ali, Jana Sheikh ;
Qiblawey, Yazan ;
Alassi, Abdulrahman ;
Massoud, Ahmed M. ;
Muyeen, S. M. ;
Abu-Rub, Haitham .
IEEE ACCESS, 2025, 13 :39912-39934
[5]  
Alrajhi H., 2025, J. Umm Al-Qura Univ. Eng. Archit., DOI [10.1007/s43995-025-00132-1, DOI 10.1007/S43995-025-00132-1]
[6]   PID control system analysis, design, and technology [J].
Ang, KH ;
Chong, G ;
Li, Y .
IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, 2005, 13 (04) :559-576
[7]  
[Anonymous], 2018, IEEE STANDARD 1547 2, P1, DOI [DOI 10.1109/IEEESTD.2018.8332112, 10.1109/IEEESTD.2018.8332112]
[8]   Advanced Control of Grid-Connected Microgrids: Challenges, Advances, and Trends [J].
Babayomi, Oluleke ;
Li, Yu ;
Zhang, Zhenbin ;
Park, Ki-Bum .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2025, 40 (06) :7681-7708
[9]  
Buso S., 2022, Digital Control in Power Electronics
[10]   An active damping control strategy for suppressing LCL resonant point migration for three-phase grid-tied inverter [J].
Chen, Dongdong ;
Zhang, Shengqi ;
Lin, Hongyi .