Load shedding scheme optimization based on load voltage and reactive power

被引:0
作者
Li, Ye [1 ]
Zhang, Baohui [1 ]
机构
[1] Xi'an Jiaotong University, Xi'an
来源
Dianli Zidonghua Shebei/Electric Power Automation Equipment | 2015年 / 35卷 / 06期
关键词
Adaptive control; Electric power systems; Frequency stability; Load shedding; Stability; Transient voltage stability;
D O I
10.16081/j.issn.1006-6047.2015.06.016
中图分类号
学科分类号
摘要
An index of shedding load allocation considering the reactive power variation and voltage deviation of nodal load is deduced based on the first-order model of induction motor, which denotes physically the equivalent susceptance change of nodal load, reflecting the proportion of induction motor in the nodal load and the influence of load model on the transient voltage stability. It is used to allocate the shedding load to each node and an adaptive load shedding scheme considering the system frequency, load voltage and reactive power response is proposed. The simulative results of IEEE 39-bus system show that, compared with the classical adaptive load shedding scheme, the proposed scheme can better guarantee the voltage and frequency stability of power system after big disturbance. ©, 2015, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:106 / 111
页数:5
相关论文
共 19 条
[1]  
Xue Y., Space-time cooperative framework for defending blackout: part III optimization and coordination of defense lines, Automation of Electric Power Systems, 30, 3, pp. 1-10, (2006)
[2]  
Dun D., Xu X., Wu Z., Realization of optimal strategy for power system low-frequency and low-voltage load reduction, Electric Power Automation Equipment, 26, 4, pp. 28-30, (2006)
[3]  
Sun H., Tang Y., Ma S., A commentary on definition and discussion of power system stability, Power System Technology, 30, 17, pp. 31-35, (2006)
[4]  
Song Z., Liu J., Liu Y., Et al., WAMS-based adaptive UFLS considering dynamic correction, Electric Power Automation Equipment, 34, 4, (2014)
[5]  
Fu X., Wang X., Du Z., Voltage stability study status and prospects in power systems, Electric Power Automation Equipment, 25, 2, pp. 1-9, (2005)
[6]  
De Ra Ree J., Centeno V., Thop J.S., Et al., Synchronized phasor measurement applications in power systems, IEEE Transactions on Smart Grid, 1, 1, pp. 20-27
[7]  
Glavic M., Van Thierry T., Wide-area detection of voltage instability from synchronized phasor measurements, IEEE Transactions on Power Systems, 24, 3, pp. 1408-1416, (2009)
[8]  
Prasetijo D., Lachs W.R., Sutanto D., A new load shedding scheme for limiting underfrequency, IEEE Transactions on Power Systems, 9, 3, pp. 1371-1378, (1994)
[9]  
Seethalekshmi K., Singh S.N., Srivastava S.C., WAMS assisted frequency and voltage stability based adaptive load shedding, IEEE Power and Energy Society General Meeting, pp. 1-8, (2009)
[10]  
Seethalekshmi K., Singh S.N., Srivastava S.C., A synchro-phasor assisted frequency and voltage stability based load shedding scheme for self-healing of power system, IEEE Transactions on Smart Grid, 2, 2, pp. 221-230, (2011)