Statistical properties and test analysis of the measured lightning invasion waves in a substation

被引:0
作者
Sima, Wenxia [1 ]
Lan, Xing [1 ]
Yang, Qing [1 ]
Yuan, Tao [1 ]
机构
[1] State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing
来源
Gaodianya Jishu/High Voltage Engineering | 2015年 / 41卷 / 01期
关键词
Actual lightning invasion wave; Breakdown characteristics; Insulation coordination; Statistical property; Time parameter; Transformer;
D O I
10.13336/j.1003-6520.hve.2015.01.003
中图分类号
学科分类号
摘要
A standard wave shape of 1.2/50 μs is often used for the insulation design and experimental researches of transformers. However, research achievements on the actual lightning invasion waves are much few, which is not good for the reasonable insulation design and assessment for transformers. In order to provide the technical basis and support for the insulation coordination of transformers, the statistical regularity of time parameters is achieved, based on the measured lightning data of an 110 kV substation. Then the breakdown characteristics of oil-paper are studied by contrast under both measured waveform and the standard one. Statistics show that the measured front time is mainly within a few microseconds, while the tail time is within a few hundred microseconds. Far different from the standard lightning wave shape of 1.2/50 μs, the front time and the tail time with 50% statistical probability of the lightning invasion waves in the substation are 20 μs and 198 μs respectively. The experimental results explain that the 50% breakdown voltage U50 and 50% voltage-time characteristic curves of oil-paper are both much different with two overvoltage waveforms. The U50 of oil-paper with the wave shape of 20/198 μs is over 10% higher than that with the standard wave shape, and the 50% voltage-time characteristic curves are above the standard ones. It is indicated that the best insulation coordination of transformers are needed to take a large number of the actual lighting data in consideration synthetically. ©, 2015, Science Press. All right reserved.
引用
收藏
页码:21 / 27
页数:6
相关论文
共 21 条
[11]  
Berlijn S., Garnacho F., Gockenbach E., Today's problems with the evaluation methods of full lightning impulse parameters as described in engineering, 11th International Symposium on High Voltage Engineering, pp. 49-52, (1999)
[12]  
Sima W., Lan H., Du L., Et al., Study on response characteristics of voltage sensor mounted at the tap of transformer bushing, Proceedings of the CSEE, 26, 21, pp. 172-176, (2006)
[13]  
Couper I.D., Cornick K.J., Guan Z.C., The effect of oscillatory switching surges on the breakdown of non-uniform gaps, Proceedings of Second International Conference on Properties and Applications of Dielectric Materials, pp. 156-159, (1988)
[14]  
Okabe S., Evaluation of breakdown characteristics of oil-immersed transformers under non-standard lightning impulse waveforms-definition of non-standard lightning impulse waveforms and insulation characteristics for waveforms including pulses, IEEE Transactions on Dielectrics and Electrical Insulation, 14, 1, pp. 146-155, (2007)
[15]  
Shindo T., Suzuki T., A new calculation method of breakdown voltage-time characteristics of long air gaps, IEEE Transactions on Power Apparatus and Systems, 104, 6, pp. 1556-1563, (1985)
[16]  
Darveniza M., The generalized integration method for predicting impulse volt-time characteristics for non-standard wave shapes-a theoretical basis, IEEE Transactions on Electrical Insulation, 23, 3, pp. 373-381, (1988)
[17]  
Berger K., Anderson B., Kroeninger H., Parameters of lightning flashes, CIGRE Electra, pp. 23-37, (1975)
[18]  
GB/T 1408.1-2006 Insulation electric strength test method part 1: tests at power frequencies, (2006)
[19]  
Liang X., High Voltage Engineering, pp. 45-48, (2003)
[20]  
Balaji S.P., Sheema I.P.M., Krithika G., Et al., Effect of repeated impulses on transformer insulation, IEEE Transactions on Dielectrics and Electrical Insulation, 18, 6, pp. 2069-2073, (2011)