Research on the Movement and Partial Discharge Characteristic of Free Metal Particles in GIS

被引:1
作者
Zhao, Ke [1 ]
Ma, Jingtan [1 ]
Gao, Shan [1 ]
Li, Hongtao [1 ]
Li, Yujie [1 ]
Xiao, Hanyan [1 ]
机构
[1] State Grid Jiangsu Elect Power Res Inst, State Grid Lab GIS Operat & Maintenance Technol, Nanjing, Peoples R China
来源
2021 IEEE 4TH INTERNATIONAL CONFERENCE ON RENEWABLE ENERGY AND POWER ENGINEERING, REPE | 2021年
关键词
GIS; free metal particle; movement; partial discharge; RISK-ASSESSMENT; VOLTAGE;
D O I
10.1109/REPE52765.2021.9617028
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Free metal particles are one of the main threats to the insulation reliability of gas-insulated switchgear (GIS). Under the action of electric field force and applied voltage, the presence of metal particles will cause the spatial electric field distortion of the GIS, which in turn leads to the degradation of the insulation performance of the GIS. In this paper, a simulation calculation model for charging, force, and movement of free metal particles in UHV GIS is established, and the movement and charging laws of particles under power voltage are studied. The results show that the spatial position distribution of particle movement is mainly in the middle area of the bottom of the GIS enclosure. The spatial position density distribution gradually decreases from the central area of the enclosure bottom to the surrounding space area. As the amplitude of the applied voltage increases, the horizontal and vertical displacements of the particles gradually increase. The maximum horizontal and vertical displacements of the particles gradually decrease with the increase of the particle radius. The particles will be charged and discharged at the full voltage phase. The particles discharge more concentrated at the voltage peak, and the discharge amount is the largest. The simulation results are basically consistent with the experimental results.
引用
收藏
页码:76 / 80
页数:5
相关论文
共 20 条
[1]  
[Anonymous], 1998, Electra, V176, P67
[2]   PARTICLE-INITIATED BREAKDOWN BETWEEN COAXIAL ELECTRODES IN COMPRESSED SF6 [J].
COOKSON, AH ;
FARISH, O .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1973, PA92 (03) :871-876
[3]   PARTICLE-INITIATED BREAKDOWN CHARACTERISTICS AND RELIABILITY IMPROVEMENT IN SF6 GAS INSULATION [J].
ENDO, F ;
YAMAGIWA, T ;
ISHIKAWA, T ;
HOSOKAWA, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (01) :58-65
[4]  
Feser K, C EL INS DIEL PHON
[5]  
Hara M., 1977, Journal of Electrostatics, V2, P223, DOI 10.1016/0304-3886(77)90055-9
[6]  
He SQ, 2003, High Voltage Apparatus
[7]  
[李杰 Li Jie], 2021, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V41, P1166
[8]  
Li Xiaoang, 2022, High Voltage Engineering, V48, P2005, DOI 10.13336/j.1003-6520.hve.20210451
[9]   Acoustic Method for Multiple Free Metallic Particle Recognition in GIS/GIL [J].
Li, Xiaoang ;
Li, Jie ;
Ren, Jing ;
Lv, Yufang ;
Li, Zhibing ;
Zhang, Qiaogen .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) :2104-2111
[10]   ACOUSTIC DIAGNOSES OF GIS - FIELD EXPERIENCE AND DEVELOPMENT OF EXPERT SYSTEM [J].
LUNDGAARD, LE ;
TANGEN, G ;
SKYBERG, B ;
FAUGSTAD, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :287-294