Ultrasonic detection system for gas insulated switchgear partial discharge based on optical fiber transmission

被引:0
作者
Liu Y. [1 ]
Li Y. [2 ]
Huang S. [1 ]
Zhao T. [1 ]
机构
[1] Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense, North China Electric Power University, Baoding
[2] Wuxi Brach of Jiangsu Electric Power Maintenance Brach Company, Wuxi
来源
Gaodianya Jishu/High Voltage Engineering | 2016年 / 42卷 / 01期
关键词
Digital signal; Gas insulated switchgear; Optical fiber; Partial discharge; Ultrasonic detection method; Virtual instrument;
D O I
10.13336/j.1003-6520.hve.2016.01.024
中图分类号
学科分类号
摘要
In order to detect and analyze the insulation status of gas insulated switchgear (GIS), combing with the optical fiber transmission technology, digital signal processing technology, and ultrasonic detection technology, we designed a GIS partial discharge (PD) ultrasonic detection system based on optical fiber transmission and LabVIEW virtual instrument. The system consists of ultrasonic sensors, remote high-speed acquisition module, local module, and PC software system, and it achieves high-speed and reliable collection of PD signals through optical transmission. The PC software system is developed on the basis of accurate extraction of PD signals, and the communication between PC and PLC adopts the UDP communication protocol. The system can collect and store ultrasonic PD signals, and it can locate faults in real time through analyzing the distribution of the signals in both time domain and frequency domain. We tested the proposed system in a number of substations over China, and the results proved the system to be effective in detecting PDs in GIS. © 2016, High Voltage Engineering Editorial Department of CEPI. All right reserved.
引用
收藏
页码:186 / 191
页数:5
相关论文
共 20 条
[1]  
Qiu Y., GIS Devices and Insulation Technology, pp. 2-10, (2007)
[2]  
Si W., Li J., Yuan P., Et al., Detection and identification techniques for multi-PD source in GIS, Proceedings of the CSEE, 29, 16, pp. 119-126, (2009)
[3]  
Okabe S., Yamagiwa T., Okubo H., Detection of harmful metallic particles inside gas insulated switchgear using UHF sensor, IEEE Transactions on Dielectrics and Electrical Insulation, 15, 3, pp. 701-709, (2008)
[4]  
Chen J., Liu W., Lu J., Et al., Acoustic signal characteristics of corona discharge in different location of GIS, High Voltage Engineering, 37, 12, pp. 3006-3011, (2011)
[5]  
Qi B., Li C., Hao Z., Et al., The surface partial discharge development phenomena and their characteristics of GIS insulator surface' fixed metal partials, Proceedings of the CSEE, 31, 1, pp. 101-108, (2011)
[6]  
Chen M., Ma G., Li C., Et al., Dielectric window sensor development for very fast transient overvoltage measurement in gas insulated switchgear, High Voltage Engineering, 40, 3, pp. 897-903, (2014)
[7]  
Bolin P., Koch H., Introduction and applications of gas insulated substation (GIS), IEEE Power Engineering Society General Meeting, pp. 920-926, (2005)
[8]  
Li D., Liang J., Bu K., Et al., Ultrasonic detection of partial discharge in typical defects in GIS, High Voltage Apparatus, 45, 1, pp. 72-75, (2009)
[9]  
Zhang T., Hu Y., Li Q., Et al., Combined ultrasonic and electrical detection system for GIS partial discharge based on virtual instrument, High Voltage Apparatus, 48, 11, pp. 43-49, (2012)
[10]  
Wu Z., Li C., Qi B., Et al., Partial discharge detection for GIS: a comparison of sensitivity between UHF and ultrasonic, Modern Electric Power, 27, 3, pp. 31-36, (2010)