Analytical model for real-time calculating hot-spot temperature of main transformer

被引:0
作者
Yang Z. [1 ]
Wu Y. [2 ]
Wang J. [1 ]
Cui L. [1 ]
Jiang C. [1 ]
Zhu H. [2 ]
Ge L. [1 ]
机构
[1] Jiangsu Collaborative Innovation Center of Smart Distribution Network, Nanjing Institute of Technology, Nanjing
[2] State Grid Jiangsu Electric Power Company, Nanjing
来源
Dianli Zidonghua Shebei/Electric Power Automation Equipment | 2016年 / 36卷 / 11期
基金
中国国家自然科学基金;
关键词
Analytical model; Electric transformers; Equivalent thermal circuit; Hot-spot temperature; Main transformer; Top-layer oil temperature; Winding time constant;
D O I
10.16081/j.issn.1006-6047.2016.11.022
中图分类号
学科分类号
摘要
An analytical model based on the equivalent thermal circuit of top-layer oil and winding is proposed, which calculates the hot-spot temperature of oil-immersed main transformer in real time according to the acquired data of its load factor and top oil temperature. A corresponding scheme for determining the winding time-constant is also proposed. Case calculation and analysis are carried out for a 334 MV·A/500 kV main transformer and the results are compared with those by the hot-spot temperature calculation formula of GB/T15164-1994, which show the effectiveness and accuracy of the proposed model and scheme. The defect of the hot-spot temperature formula of GB/T 15164-1994 is pointed out. © 2016, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:147 / 151
页数:4
相关论文
共 13 条
[1]  
Riberiro A.B.L., Eira N.F., Sousa J.M., Et al., Multipoint fiber-optic hot-spot sensing network integrated into high power transformer for continuous monitoring, IEEE Sensors Journal, 8, 7, pp. 1264-1267, (2008)
[2]  
Liu J., The FBG monitoring principle of transformer internal temperature and the improved method for calculation of the hot-spot temperature, (2009)
[3]  
Wen B., Liu S., Feng J., Et al., Two dimensional simulation analysis of winding temperature field of oil-immersed power transformer, Transformer, 46, 9, pp. 35-38, (2009)
[4]  
Chen W., Su X., Sun C., Et al., Temperature distribution calculation based on FVM for oil-immersed power transformer windings, Electric Power Automation Equipment, 31, 6, pp. 23-27, (2011)
[5]  
Faiz J., Sharifian M.B.B., Fakhri A., Two-dimensional finite element thermal modeling of an oil-immersed transformer, European Transactions on Electrical Power, 18, 6, pp. 577-594, (2008)
[6]  
IEEE guide for loading mineral-oil-immersed transformers: IEEE Std C57.91-1995, (1996)
[7]  
Jiang T., Li J., Chen W., Et al., Thermal model for hot spot temperature calculation in oil-immersed transformers, High Voltage Engineering, 35, 7, pp. 1635-1640, (2009)
[8]  
Swift G., Molinski T.S., Bray R., A fundamental approach to transformer thermal modeling I: theory and equivalent circuit, IEEE Transactions on Power Delivery, 16, 2, pp. 171-175, (2001)
[9]  
Radakovic Z., Feser K., A new method for the calculation of the hot-spot temperature in power transformers with ONAN cooling, IEEE Transactions on Power Delivery, 18, 4, pp. 1284-1292, (2003)
[10]  
Susa D., Lehtonen M., Nordman H., Dynamic thermal modeling of power transformers, IEEE Transactions on Power Delivery, 20, 1, pp. 197-204, (2005)