Three-phase four-wire shut active power filter with coupled inductors

被引:1
作者
Chen, Xiao [1 ,2 ]
Chen, Heng-Lin [1 ]
Chen, Guo-Zhu [1 ]
机构
[1] College of Electrical Engineering, Zhejiang University, Hangzhou
[2] School of Automation and Electrical Engineering, Zhejiang University of Science and Technology, Hangzhou
来源
Zhejiang Daxue Xuebao (Gongxue Ban)/Journal of Zhejiang University (Engineering Science) | 2015年 / 49卷 / 08期
关键词
Active power filter; Compensation accuracy; Coupled inductor; Decoupling equivalent circuit; Three-phase four-wire;
D O I
10.3785/j.issn.1008-973X.2015.08.018
中图分类号
学科分类号
摘要
A configuration of three-phase four-wire shunt active power filter (SAPF) which included the coupled inductors and the neutral wire filter inductors was proposed in this paper to resolve the problems of increasing equipment measurement and cost due to using three uncoupled inductors in the output filter of the traditional SAPF. The positive-sequence, negative-sequence, zero-sequence equivalent models of the three-phase three-column coupled inductor which included assistant winding were deduced in detail. The decoupling equivalent circuits of the system were obtained. And the controllers of system were designed. Compared with the traditional three-phase four-wire SAPF, simulation results under mostly working conditions show not only better steady-state compensation accuracy and stronger ability of restraining switching ripple of neutral wire but also better dynamic performances for the proposed configuration. Experimental results verify the feasibility of the proposed configuration. ©, 2015, Zhejiang University. All right reserved.
引用
收藏
页码:1529 / 1536
页数:7
相关论文
共 12 条
[1]  
Akagi H., New trends in active filters for power conditioning, IEEE Transactions on Industry Applications, 32, 6, pp. 1312-1322, (1996)
[2]  
Orts S., Gimeno-Sales F.J., Abellan A., Et al., Achieving maximum efficiency in three-phase systems with a shunt active power compensator based on IEEE Std. 1459, IEEE Transactions on Power Delivery, 23, 2, pp. 812-822, (2008)
[3]  
Liserre M., Blaabjerg F., Design and control of an LCL-filter-based three-phase active rectifier, IEEE Transactions on Industry Applications, 41, 5, pp. 1281-1291, (2005)
[4]  
Wu J., Xu D.-G., He N., Research on LCL filter applied to shunt active power filter, Electric Power Automation Equipment, 1, pp. 17-20, (2007)
[5]  
Chen L.-L., Xiao L., Hu W.-B., Et al., Circulating-current restraining method Based on coupled inductors in parallel inverter system, Journal of Nanjing University of Aeronautics & Astronautics, 36, 2, pp. 205-209, (2004)
[6]  
Shin D., Lee J.P., Lee K.J., Et al., 1.5MVA grid-connected interleaved inverters using coupled inductors for wind power generation system, Energy Conversion Congress and Exposition (ECCE), pp. 4689-4696, (2013)
[7]  
He C., Xie C., Chen G.-Z., Study on Shunt Active Power Filters with Coupled Inductors, Proceedings of the 2011 IEEE International Symposium on Industrial Electronics (ISIE2011), pp. 438-443, (2011)
[8]  
Dai N.-Y., Wong M.-C., Han Y.-D., Application of a three-level NPC inverter as a three-phase four-wire power quality compensator by generalized 3DSVM, IEEE Trans. on Power Electronics, 21, 2, pp. 51-58, (2006)
[9]  
Tang J., Zou X.-D., She X., Et al., A Research on neutral-point potential balancing control strategy for three-phase four-wire tri-level three-leg APFs, Proceedings of the CSEE, 29, 24, pp. 40-48, (2009)
[10]  
Gu W.-F., The three-phase reactor applied to three-phase four-wire grid-connected inverter