Performance evaluation of natural draft dry cooling towers and pre-cooled natural draft dry cooling towers in concentrated solar power plants

被引:0
作者
Ruiz, J. [1 ]
Gasco, C. [1 ]
Opolot, M. [2 ]
Hooman, K. [3 ]
机构
[1] Miguel Hernandez Univ Elche, Engn Res Inst Elche, Elche, Spain
[2] Cent Queensland Univ, Ctr Hydrogen & Renewable Energy, Gladstone Marina, Qld, Australia
[3] Delft Univ Technol, Dept Proc & Energy, Leeghwaterstr 39, NL-2628 CB Delft, Netherlands
关键词
Natural draft dry cooling tower; Evaporative cooling; Concentrated solar power; Condenser; Energy efficiency; Water consumption; INLET AIR; WATER SPRAY; MEDIA; DESIGN; SYSTEM; FLOW;
D O I
10.1016/j.energy.2025.137362
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study examines the integration of Natural Draft Dry Cooling Towers (NDDCT) and pre-cooled NDDCT as innovative heat rejection systems for a 50 MW Concentrated Solar Power (CSP) plant, comparing their performance against conventional alternatives: Mechanical Draft Wet Cooling Towers (MDWCT), Air-Cooled Condensers (ACC), and hybrid pre-cooled ACC systems (media pads and spray nozzles). Analytical models for the cooling systems and their interaction with the CSP plant were developed and validated against results reported in the literature. Using hourly temporal resolution and real climatic data from Granada, Spain, the analysis evaluates the annual impact of these systems on energy generation and water consumption. The results demonstrate that pre-cooled NDDCT increases annual power generation by approximately 1400 MWh compared to NDDCT, with substantial performance improvements during peak summer conditions. Although MDWCT achieves the highest efficiency, it comes at the cost of significant water consumption. Pre-cooled NDDCT stands out as a promising hybrid solution, balancing improved condensation performance (only 2.9% less efficiency compared to MDWCT) with minimal water usage (76.7% less than MDWCT). This study provides valuable insights for optimising CSP plant performance in arid regions, advancing beyond previous efforts in the literature.
引用
收藏
页数:12
相关论文
共 34 条
[1]   Parametric study on spray cooling system for optimising nozzle design with pre-cooling application in natural draft dry cooling towers [J].
Alkhedhair, Abdullah ;
Jahn, Ingo ;
Gurgenci, Hal ;
Guan, Zhiqiang ;
He, Suoying .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2016, 104 :448-460
[2]   Water spray for pre-cooling of inlet air for Natural Draft Dry Cooling Towers - Experimental study [J].
Alkhedhair, Abdullah ;
Guan, Zhiqiang ;
Jahn, Ingo ;
Gurgenci, Hal ;
He, Suoying .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2015, 90 :70-78
[3]   Numerical simulation of water spray for pre-cooling of inlet air in natural draft dry cooling towers [J].
Alkhedhair, Abdullah ;
Gurgenci, Hal ;
Jahn, Ingo ;
Guan, Zhiqiang ;
He, Suoying .
APPLIED THERMAL ENGINEERING, 2013, 61 (02) :416-424
[4]  
[Anonymous], 2002, COMP ALTERNATE COOLI
[5]  
Cooperman A, 2012, ASHRAE J, V54, P65
[6]   Energetic, exergetic and environmental (3E) analyses of different cooling technologies (wet, dry and hybrid) in a CSP thermal power plant [J].
Cutillas, C. G. ;
Ruiz, J. ;
Asfand, F. ;
Patchigolla, K. ;
Lucas, M. .
CASE STUDIES IN THERMAL ENGINEERING, 2021, 28
[7]   Investigation on the control mechanism of spray pre-cooling the inlet air of natural draft dry cooling tower [J].
He, Suoying ;
Li, Yang ;
Wang, Mingwei ;
Wang, Aiping ;
Alkhedhair, Abdullah M. ;
Guan, Hongjun ;
Wu, Xuehong ;
Shi, Yuetao ;
Gao, Ming .
APPLIED THERMAL ENGINEERING, 2022, 217
[8]   Selection of wetted media for pre-cooling of air entering natural draft dry cooling towers [J].
He, Suoying ;
Xu, Yi ;
Zhang, Guanhong ;
Hooman, Kamel ;
Gao, Ming .
APPLIED THERMAL ENGINEERING, 2017, 114 :857-863
[9]   Comparative study on the performance of natural draft dry, pre-cooled and wet cooling towers [J].
He, Suoying ;
Gurgenci, Hal ;
Guan, Zhiqiang ;
Hooman, Kamel ;
Zou, Zheng ;
Sun, Fengzhong .
APPLIED THERMAL ENGINEERING, 2016, 99 :103-113
[10]   Experimental study of the application of two trickle media for inlet air pre-cooling of natural draft dry cooling towers [J].
He, Suoying ;
Guan, Zhiqiang ;
Gurgenci, Hal ;
Hooman, Kamel ;
Lu, Yuanshen ;
Alkhedhair, Abdullah M. .
ENERGY CONVERSION AND MANAGEMENT, 2015, 89 :644-654