Fault current handling in large-scale MMC-HVDC systems: an improved approach with DC circuit breaker and fault current limiter

被引:0
作者
Chandio, Rashid Hussain [1 ]
Shah, Madad Ali [1 ]
Memon, Abdul Aziz [1 ]
Ali, Khawaja Haider [1 ]
Soomro, Jahangeer Badar [1 ]
Alamri, Basem [2 ]
Althobaiti, Ahmed [2 ]
Alqarni, Mohammed [3 ]
机构
[1] Department of Electrical Engineering, Sukkur IBA University, Sukkur
[2] Department of Electrical Engineering, College of Engineering, Taif University, Taif
[3] Department of Electrical Engineering, College of Engineering, University of Business and Technology (UBT), Jeddah
关键词
DCCBs; FCL; hybrid CB; MMC-HVDC; protection; VSC-HVDC;
D O I
10.3389/fenrg.2025.1430142
中图分类号
学科分类号
摘要
Designing Voltage Source Converter (VSC)-based DC grids presents a significant challenge in providing dependable and cost-effective protection against short-circuit faults. Given the increased vulnerability of high-voltage DC (HVDC) lines to the faults, there is a dire need for enhanced protection equipment capable of effectively handling fault currents. By limiting the rapid increase in fault current, fault current limiters (FCLs) reduce the requirement for complex DC circuit breakers (DCCBs) design in order to isolate faults. This paper presents a novel Hybrid FCL for the protection of large scale VSC-HVDC. It provides a comprehensive analysis of DCCBs and their impact on VSC-HVDC projects with and without FCLs. It further analyses an extensive discussion comparing DCCBs equipped with FCLs to those without FCLs. For simulation analysis, an equivalent circuit modeling approach of the Zhoushan HVDC Project is used to analyze current behavior of FCL-equipped breakers. The paper presents the circuit diagram and operational principles of the proposed FCL. Subsequently, it analyzes the FCL performance with its current limiting features and outlines the parameter design requirements necessary for its implementation. Simulation results utilizing PSCAD/EMTDC are provided to validate various aspects of this research. Further, the performance of the proposed FCL is compared with existing solutions proposed in the literature. From theoretical and simulation validations, it is concluded that DCCBs equipped with FCLs outperform conventional DCCBs without FCLs for higher-rated VSC-HVDC projects. Copyright © 2025 Chandio, Shah, Memon, Ali, Soomro, Alamri, Althobaiti and Alqarni.
引用
收藏
相关论文
共 33 条
[1]  
Ahmad M., Wang Z., Shafique M., Nadeem M.H., Significance of fault-current-limiters and parameters optimization in HVDC circuit breakers for increased capacity of VSC-HVDC transmission networks application, Energy Rep, 8, pp. 878-892, (2022)
[2]  
Ahmad M., Wang Z., Zhang Y., High-voltage DC circuit breaker with gradual fault-current limitation mechanism for VSC-HVDC applications, Int. Trans. Electr. Energy Syst, 30, 8, pp. 1-16, (2020)
[3]  
Barnes M., Vilchis-Rodriguez D.S., Pei X., Shuttleworth R., Cwikowski O., Smith A.C., HVDC circuit breakers-A review, IEEE Access, 8, pp. 211829-211848, (2020)
[4]  
Callavik M., Blomberg A., Hafner J., Jacobson B., Break-through!: ABB’s hybrid HVDC breaker, an innovation breakthrough enabling reliable HVDC grids, ABB Rev, 2, pp. 7-13, (2013)
[5]  
Chen L., Li G., Chen H., Qiao X., Ding M., Hu R., Et al., Combinatorial multi-objective optimization of resistive SFCL and DC circuit breaker in hybrid HVDC transmission system, IEEE Trans. Appl. Supercond, 31, 8, pp. 1-6, (2021)
[6]  
Chen L., Zhang X., Qin Y., Chen H., Shen Q., Xu Y., Et al., Application and design of a resistive-type superconducting fault current limiter for efficient protection of a DC microgrid, IEEE Trans. Appl. Supercond, 29, 2, pp. 1-7, (2019)
[7]  
Dao V.Q., Lee J.I., Kim C.S., Park M., Melaccio U., Design and performance analysis of a saturated iron-core superconducting fault current limiter for dc power systems, Energies, 13, 22, (2020)
[8]  
Didier G., Bonnard C.H., Lubin T., Leveque J., Comparison between inductive and resistive SFCL in terms of current limitation and power system transient stability, Electr. Power Syst. Res, 125, pp. 150-158, (2015)
[9]  
Fu Z., Sima W., Yang M., Sun P., Yuan T., Wang X., Et al., A mutual-inductance-type fault current limiter in MMC-HVDC systems, IEEE Trans. Power Deliv, 35, 5, pp. 2403-2413, (2020)
[10]  
Hamada A.M., Essam E., Abdalfatah S., Awad H., Development of a DC hybrid fault-current limiting and interrupting device for microgrid applications with a new approach for current-limiting capability, Phys. C Supercond. its Appl, 613, September, (2023)