MISOCP Model for Reactive Power Optimization With Nonuniform Voltage Regulators in Unbalanced Three-Phase Active Distribution Networks

被引:0
作者
Mu, Chenggang [1 ]
Ding, Tao [1 ]
Wang, Shunqi [1 ]
Jia, Wenhao [1 ]
Shahidehpour, Mohammad [2 ]
Luo, Zhao [3 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Shaanxi, Peoples R China
[2] IIT, Dept Elect & Comp Engn, Chicago, IL 60616 USA
[3] Kunming Univ Sci & Technol, Sch Elect Engn, Kunming 650500, Yunnan, Peoples R China
基金
中国国家自然科学基金;
关键词
Reactive power; Programming; Vectors; Voltage control; Optimization; Load flow; Computational modeling; Static VAr compensators; Regulators; MISO; Reactive power optimization; active distribution network; three-phase unbalance; nonuniform voltage regulator; mixed-integer second-order cone programming; FLOW; RELAXATIONS; TRANSFORMERS;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Reactive power optimization (RPO) is a key task in the operation and control of active distribution networks (ADNs). The nonlinear power flow constraints and the integers introduced by voltage regulator (VR) constraints make the nonconvex RPO model difficult to solve. In this paper, a RPO model is proposed considering the nonuniform tap ratios of VRs. The three phases in VRs are independently controlled and the phase coupling effects are strictly considered. Moreover, to deal with the bilinear relationship among continuous complex voltage phasors and discrete tap ratios, the voltage phasor matrix is decoupled into real and imaginary parts, and a status variable method is proposed to exactly linearize the bilinear terms. Further, the nonlinear power flow constraints are relaxed to a set of second-order cone constraints without neglecting the coupling effect among the three phases and are proved to be equivalent to the semi-definite constraints, which does not require the rank-1 verification and is more efficient and scalable. Thus, the original nonconvex RPO for three-phase unbalanced ADNs is simplified to a mixed-integer second-order cone programming (MISOCP) model. Case studies validate the model's effectiveness, and the computational efficiency meets practical requirements. Note to Practitioners-This paper simplifies the complex problem of reactive power optimization for active distribution networks with unbalanced three-phase power flows. We offer a novel RPO model improving the typically nonconvex and nonlinear optimal power flow problem, and addressing the particular challenges imposed by voltage regulators optimization with nonuniform tap ratios. Independent control of the VR phases and accurate incorporation of phase coupling effects have been realized, greatly simplifying the optimization process. The transformation of nonlinear power flow constraints into a computationally efficient set of second-order cone constraints eliminates the need for cumbersome rank-1 verification. Our mixed-integer second-order cone programming model integrates smoothly with standard optimization procedures, improving voltage regulation and network stability. The effectiveness and efficiency of the approach have been validated in case studies, offering a viable tool for industry application.
引用
收藏
页码:10118 / 10129
页数:12
相关论文
共 31 条
[1]  
Alsaleh I, 2019, IEEE POW ENER SOC GE, DOI 10.1109/PESGM40551.2019.8973879
[2]   Multi-Time Co-optimization of Voltage Regulators and Photovoltaics in Unbalanced Distribution Systems [J].
Alsaleh, Ibrahim ;
Fan, Lingling .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2021, 12 (01) :482-491
[3]   A New Remote Tap Position Estimation Approach for Open-Delta Step-Voltage Regulator in a Photovoltaic Integrated Distribution Network [J].
Bai, Feifei ;
Yan, Ruifeng ;
Saha, Tapan Kumar ;
Eghbal, Daniel .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (04) :4433-4443
[4]   Optimal Power Flow With Step-Voltage Regulators in Multi-Phase Distribution Networks [J].
Bazrafshan, Mohammadhafez ;
Gatsis, Nikolaos ;
Zhu, Hao .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2019, 34 (06) :4228-4239
[5]  
Bose Subhonmesh, 2011, 2011 49th Annual Allerton Conference on Communication, Control, and Computing (Allerton), P1342
[6]   A New Model for Resilient Distribution Systems by Microgrids Formation [J].
Ding, Tao ;
Lin, Yanling ;
Li, Gengfeng ;
Bie, Zhaohong .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (05) :4145-4147
[7]   A Two-Stage Robust Optimization for Centralized-Optimal Dispatch of Photovoltaic Inverters in Active Distribution Networks [J].
Ding, Tao ;
Li, Cheng ;
Yang, Yongheng ;
Jiang, Jiangfeng ;
Bie, Zhaohong ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2017, 8 (02) :744-754
[8]   Optimal operation of smart distribution networks: A review of models, methods and future research [J].
Evangelopoulos, Vasileios A. ;
Georgilakis, Pavlos S. ;
Hatziargyriou, Nikos D. .
ELECTRIC POWER SYSTEMS RESEARCH, 2016, 140 :95-106
[9]  
Farivar M, 2013, IEEE T POWER SYST, V28, P2565, DOI 10.1109/TPWRS.2013.2255318
[10]  
Gan Lingwen, 2014, 2014 POWER SYSTEMS C