A Study on the Generation Characteristics of Decomposition Gases for Insulating Oil of Transformer Bushing

被引:0
作者
Jun, Tae-Hyun [1 ]
Kwak, Byeong-Sub [1 ]
Kim, Ah-Reum [1 ]
Lim, Byung-Hun [1 ]
Park, Hyun-Joo [1 ]
机构
[1] Korea Electric Power Research Institute, Korea Electric Power Corporation
关键词
Accelerated ageing; Decomposition gas; Diagnosis criteria; Oil impregenated bushing; Power Transformer;
D O I
10.5370/KIEE.2025.74.2.326
中图分类号
学科分类号
摘要
In recent years, the number of failures caused by oil impregenated paper(OIP) bushings applied to long-term power transformers has been increasing, and some of them have progressed to fires, increasing the possibility of facility damage. As OIP bushings are more than 70% of the long-term bushings in operation, there is a high probability of fire in case of failure, so it is necessary to develop diagnostic technology for aging bushings. Although KEPCO is implementing insulation oil gas analysis to prevent the continued occurrence of failures and recurrence of failures due to bushing insulation breakdown. However, since KEPCO currently does not have its own bushing oil gas maintenance standards, it is necessary to establish management standards that reflect the differences in insulation oil types among manufacturers. Therefore, in this study, we evaluated the generation characteristics of major decomposed gases by failure type based on KEPCO's accumulated bushing dissolved gas analysis database for major bushing manufacturers in operation, bushing internal dismantling inspection, and accelerated aging experiments for each manufacturer. Based on this, it is expected to contribute to the establishment of abnormal diagnosis criteria for OIP bushings and improvement of facility inspection efficiency. Copyright © The Korean Institute of Electrical Engineers.
引用
收藏
页码:326 / 331
页数:5
相关论文
共 6 条
[1]  
ACTIS Riccardo, MAINA Riccardo, TUMIATTI Vander, Diagnostics of HV bushings through oil sampling and analysis, TRANSFORMERS MAGAZINE, pp. 24-30, (2017)
[2]  
Insulated bushings - Guide for the interpretation of dissolved gas analysis (DGA) in bushings where oil is the impregnating medium of the main insulation, (1998)
[3]  
Mineral oil-filled electrical equipment in service - Guidance on the interpretation of dissolved and free gases analysis, (2015)
[4]  
Liao Rui-jin, Hu -de, Yang Li-jun, Xu Zuo-ming, The Investigation on Thermal Aging Characteristics of Oil-Paper insulation in Bushing, J Electr Eng Technol, 10, 3, pp. 1114-1123, (2021)
[5]  
Gao S., Yang L., Ke T., Ageing characteristics and lifetime model of oil-paper insulation for oil-immersed paper condenser bushing, High voltage, 6, 2, pp. 278-290, (2021)
[6]  
Zhou Dan, Et al., Experience gained in fault diagnosis and tear-down analysis of transformer bushings, 2019 IEEE 3rd International Electrical and Energy Conference (CIEEC), pp. 1691-1694, (2019)