Pilot protection of active distribution network based on novel positive-sequence fault component comprehensive impedance

被引:0
作者
Wang, Yabing [1 ]
Tong, Xiaoyang [1 ]
Zhao, Zibin [1 ]
Dong, Xingxing [1 ]
Manzoor, Sohail [1 ]
机构
[1] School of Electrical Engineering, Southwest Jiaotong University, Chengdu
来源
Dianli Zidonghua Shebei/Electric Power Automation Equipment | 2025年 / 45卷 / 02期
关键词
active distribution network; distributed generator; new comprehensive impedance; pilot protection; positive-sequence fault component; relay protection; short fault;
D O I
10.16081/j.epae.202411020
中图分类号
TM72 [输配电技术];
学科分类号
摘要
The access of distributed generators to distribution network changes the topology of the traditional distribution network, which changes fault characteristics, and conventional distribution network current protection will lose its selectivity. Aiming at this problem,a novel protection method based on the comprehensive impedance of positive sequence fault component is proposed. The fault characteristics of positive-sequence fault voltages and currents are analyzed when internal and external faults occur in the line with different types of distributed generations. The positive-sequence fault components of voltage and current at both ends of the section are used to calculate the estimated line impedances on both sides, the new comprehensive impedance is obtained by their subtraction. Taking the ratio of comprehensive impedance to line impedance as impedance coefficient, and then the protection criterion of internal and external short circuit faults is constructed. The effectiveness of proposed protection algorithm is verified by a large number of Simulation experiments. It can accurately detect short circuit faults, and is not affected by fault type, fault location, type and permeability of distributed generator, distributed generator exit, and has high sensitivity and strong resistance to transition resistance. © 2025 Electric Power Automation Equipment Press. All rights reserved.
引用
收藏
页码:103 / 109
页数:6
相关论文
共 21 条
[1]  
TAN Xiandong, LIU Jun, XU Zhicheng, Et al., Power supply and (Jemand balance during the 14th five-year plan period under the goal of carbon emission peak and carbon neutrality, Electric Power, 54, 5, pp. 1-6, (2021)
[2]  
ZHOU Chenghan, Guibin U, Xiaogong DU, Et al., A pilot protection method based on positive sequence fault oomponent current for active distribution networks [Jj, Proceedings of the CSEE, 40, 7, pp. 2102-2112, (2020)
[3]  
CHEN Kexin, XIN Huanhai, GAO Huisheng, Et al., Nodal fre-quency analysis method for renewable energy power System considering multimodal eomponenls, Electric Power Automation Equipment, 43, 10, pp. 136-144, (2023)
[4]  
Zhaohong BIE, Chaofan LIN, LI Gengfeng, Et al., Development and prospect of resilient power System in the context of energy transition[j], Proceedings of the CSEE, 40, 9, pp. 2735-2744, (2020)
[5]  
HAN Xiao, DING Yufei, XIA Yinyu, Et al., Active distribution network protection based on negative sequence fault superim-posed network model identification [j], Electric Machines & Control Application, 50, 2, pp. 56-60, (2023)
[6]  
LIANG Yingyu, LU Zhengjie, Adaptive differential protection principle based on compensation coefficient for active distribution network [j], Power System Technology, 46, 6, pp. 2268-2275, (2022)
[7]  
MA Jing, WANG Xi, MI Chao, Et al., A new adaptive protection approach for distribution network containing distrihuted generation[j], Power System Technology, 35, 10, pp. 204-208, (2011)
[8]  
WEI Donghui, YU Shunyao, FANG Junlong, Pilot protection scheme for distribution network containing photovoltaic power based on integrated sequence current [j], Acta Energiae Solaris sinica, 42, 7, pp. 185-192, (2021)
[9]  
CHEN Xiaolong, YUAN Shu, LI Yongli, Et al., Analysis of sin-gle-phase grounding fault eharaeteristics in petal-shaped distribution network with inverter-interfaced distributed generator[j], Electric Power Automation Equipment, 42, 4, pp. 129-137, (2022)
[10]  
XU Meng, Guibin Z0U, GAO Lei, Et al., Pilot protection of positive sequence impedance for distribution network with inverter-based distributed generator [j], Automation of Electric Power Systems, 41, 12, pp. 93-99, (2017)