Overvoltages in Medium-Voltage Industrial Systems Associated With Switching High-Voltage Transformers Connected Through Insulated Cables: Analysis and Solutions

被引:0
作者
Rocha, Leonardo de Carvalho [1 ]
Borges, Thiago Trezza [1 ]
Las Casas, Fabricio [1 ]
机构
[1] Petrobras SA, BR-20011904 Rio De Janeiro, Brazil
关键词
Power transformer insulation; Surges; Integrated circuit modeling; Cables; Capacitance; Voltage; Switchgear; Circuit faults; Switches; Oil insulation;
D O I
10.1109/MIAS.2025.3559856
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This work, based on [1], presents and discusses the solutions to overvoltages experienced by the medium voltage system (13.8 kV) in an existing refinery resulting from the switching of power transformers supplied by a high voltage system (230 kV) through insulated cables. The analysis demonstrates the influence of the other feeder cables and the transient interaction between them and the switched feeder, due to their high capacitances, leading to the increase of overvoltages to values over the insulation withstand. These overvoltages exhibit high frequency and high amplitude and are primarily transferred from the high voltage side to the medium voltage side mainly through transformer capacitive couplings. This process may lead to insulation breakdown in medium voltage equipment, as confirmed by simulations and practical observations. Solutions for overvoltage mitigation, such as surge arresters and pre-insertion resistors applied to switching circuit breakers, are presented.
引用
收藏
页码:27 / 36
页数:10
相关论文
共 18 条
[1]  
[Anonymous], 2014, C370122014 IEEE
[2]  
[Anonymous], 2019, 6007112019 IEC
[3]  
[Anonymous], 2021, 622712002021 IEC
[4]  
[Anonymous], 2019, IEEE Std C37.011-2019
[5]  
Borgueti A., 2011, P INT C POW SYST TRA
[6]   MATRIX REPRESENTATION OF 3-PHASE N-WINDING TRANSFORMERS FOR STEADY-STATE AND TRANSIENT STUDIES [J].
BRANDWAJN, V ;
DOMMEL, HW ;
DOMMEL, II .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (06) :1369-1378
[7]  
Das JC, 2002, IEEE PULP P, P139, DOI 10.1109/PAPCON.2002.1015142
[8]   Validation of ATP transmission line models for a Monte Carlo study of switching transients [J].
Gomez, Pablo .
2007 39TH NORTH AMERICAN POWER SYMPOSIUM, VOLS 1 AND 2, 2007, :124-129
[9]   Study of Transformer Resonant Overvoltages Caused by Cable-Transformer High-Frequency Interaction [J].
Gustavsen, Bjorn .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) :770-779
[10]  
Hevia O. P., 2000, EEUG NEWS, V6, P19