Investigation on multi-stage compression high-temperature heat pump system based on R718 and other low GWP refrigerants

被引:0
作者
Shi, Xilong [1 ]
Zhang, Chenghu [1 ]
Liu, Yan [1 ]
Wang, Fazhong [2 ]
机构
[1] Harbin Inst Technol, Minist Ind & Informat Technol, Sch Architecture & Design, Key Lab Cold Reg Urban & Rural Human Settlement En, Harbin, Peoples R China
[2] Dunham Bush China Ind Co Ltd, Yantai, Shandong, Peoples R China
关键词
High-temperature heat pump; Multi-stage compression; R718; Excessive superheat; Coefficient of performance; Exergy efficiency; WATER;
D O I
10.1016/j.ijrefrig.2025.04.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
Under the dual-carbon strategy, electrifying industrial heating is a key trend. This study develops three types of thermodynamic cycle models for compression high-temperature heat pump (HTHP) systems. The effects of evaporation temperature on the compression characteristics of R718, R245fa, R1234ze(Z), and R1336mzz(Z) are investigated, along with an analysis of the available energy variation within the system. Results show that R718 exhibits superior thermodynamic properties compared to other refrigerants at high evaporation temperatures, with its coefficient of performance (COP) increasing from 4.70 to 5.34. However, the high pressure ratio and excessive superheat (up to 150 degrees C at 90 degrees C evaporation temperature) limits its practical application. When the lifting temperature is set at 40 degrees C, the three-stage compression (THC) system achieves an optimal performance value of 5.47, with a pressure ratio of 1.58 and exhaust superheat of 35.38 degrees C. The exergy efficiency of the three-stage compression (TWC) and THC systems using R718 is 39.6 % and 56.1 % higher than that of the single-stage compression (SC) system at a waste heat source temperature of 95 degrees C, respectively. These findings emphasize that multi-stage compression significantly enhances energy efficiency. Furthermore, this study provides valuable guidance for practical engineering applications.
引用
收藏
页码:238 / 253
页数:16
相关论文
共 45 条
[21]   Experimental assessment of the low GWP refrigerant HFO-1234ze(Z) for high temperature heat pumps [J].
Longo, Giovanni A. ;
Zilio, Claudio ;
Righetti, Giulia ;
Brown, J. Steven .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2014, 57 :293-300
[22]   Performance analysis of different single stage advanced vapor compression cycles and refrigerants for high temperature heat pumps [J].
Luo, Baojun ;
Zou, Peng .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 104 :246-258
[23]   Performance Analysis of High-temperature Two-stage Compression Heat Pump with Vapor Injection Dynamic Control [J].
Luo, Win-Jet ;
Lai, Jin-Chang ;
Hsieh, Ming-Chu ;
Huang, I-Hsing .
SENSORS AND MATERIALS, 2020, 32 (12) :4259-4275
[24]   A comprehensive review of compression high-temperature heat pump steam system: Status and trend [J].
Ma, Xudong ;
Du, Yanjun ;
Zhao, Tian ;
Zhu, Tingting ;
Lei, Biao ;
Wu, Yuting .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 164 :218-242
[25]  
Madsboell H, 2014, 11TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS (2014), P891
[26]   Theoretical evaluation of different high-temperature heat pump configurations for low-grade waste heat recovery [J].
Mateu-Ryo, Carlos ;
Navarro-Esbri, Joaquin ;
Mota-Babiloni, Adrian ;
Amat-Albuixech, Marta ;
Moles, Francisco .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 90 :229-237
[27]  
McLinden M., 1998, NIST THERMODYNAMIC T
[28]  
NIST (National Institute of Science and Technology), 2007, Standard reference database23
[29]  
Powell Peter, 2012, Air Conditioning Heating & Refrigeration News
[30]   Experimental analysis of oil flooded R410A scroll compressor [J].
Ramaraj, Sugirdhalakshmi ;
Yang, Bin ;
Braun, James E. ;
Groll, Eckhard A. ;
Horton, W. Travis .