Comparative analysis of the energy-saving potential of a hybrid deep dam water cooling system for data centers

被引:0
|
作者
Boafo, Nicholas Lamptey [1 ]
Anka, Selorm Kwaku [1 ]
Boahen, Samuel [2 ]
Choi, Jong Min [3 ]
机构
[1] Hanbat Natl Univ, Grad Sch Dept Mech Engn, Dept Mech Engn, Daejeon 34158, South Korea
[2] Kwame Nkrumah Univ Sci & Technol, Dept Mech Engn, Kumasi, Ghana
[3] Hanbat Natl Univ, Dept Mech Engn, Daejeon 34158, South Korea
关键词
Energy; Cooling; Dam water; Air-source; Data center; VAPOR COMPRESSION; CONTROL STRATEGY; SIMULATION; ECONOMIZER; AIR;
D O I
10.1016/j.enbuild.2025.115770
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Data center cooling systems are major energy consumers, operating continuously throughout the year. And because of this, the provision of low-cost cooling is challenging. In recent years, researchers have focused on integrating potential renewable energy sources to reduce energy usage in these systems. This study examines the potential for energy saving potential of a newly developed hybrid dam water cooling system for data centers, which functions in free and forced cooling modes. Firstly, the study conducted an experimental comparison between the performance of the hybrid system and that of a conventional air source cooling system based on variations in heat source temperatures. Both systems were then modelled in EnergyPlus using data from the Soyang Dam in Chuncheon, South Korea, to assess their seasonal and annual energy consumption. Compared to the conventional system, the hybrid dam water cooling system had approximately 76.2 %, 66 %, and 21.6 % energy savings in the winter, spring, and summer seasons, respectively, and 48 % annual energy savings. These savings are attributed to the efficient free cooling mode of the system, the stable temperature of the heat source, and the reduced compressor cycling frequency in forced mode. Furthermore, compared to the hybrid system in forced cooling, the energy consumption of the hybrid system in free cooling mode was insignificantly affected by the changes in dam water temperature. This confirms the energy saving potential of the hybrid system in free cooling mode.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] Energy-saving analysis of a case data center with a pump-driven loop heat pipe system in different climate regions in China
    Zhou, Feng
    Li, Cuicui
    Zhu, Wanpeng
    Zhou, Jing
    Ma, Guoyuan
    Liu, Zhongliang
    ENERGY AND BUILDINGS, 2018, 169 : 295 - 304
  • [32] A Data Center Energy-saving System and Method based on Virtual IT Resource Distribution Technology
    Liang, Yan
    Wang, Fuqiang
    Li, Gang
    Fang, Xing
    Ge, Changrong
    Zhao, Xinyan
    MECHANICAL ENGINEERING AND INSTRUMENTATION, 2014, 526 : 297 - +
  • [33] Verification of the energy-saving effect of the district heating and cooling system - Simulation of an electric-driven heat pump system
    Nagota, Tomoji
    Shimoda, Yoshiyuki
    Mizuno, Minoru
    ENERGY AND BUILDINGS, 2008, 40 (05) : 732 - 741
  • [34] Energy, environmental and economical saving potential of data centers with various economizers across Australia
    Khalaj, Ali Habibi
    Scherer, Thomas
    Halgamuge, Saman K.
    APPLIED ENERGY, 2016, 183 : 1528 - 1549
  • [35] Various uncertainties self-correction method for the supervisory control of a hybrid cooling system in data centers
    Wang, Jiaqiang
    Huang, Zhenlin
    Yue, Chang
    Zhang, Quan
    Wang, Peng
    JOURNAL OF BUILDING ENGINEERING, 2021, 42
  • [36] Worldwide Energy Analysis of Major Free Cooling Methods for Data Centers
    Gozcu, Ozan
    Ozada, Berk
    Carfi, Muhammed Ugur
    Erden, Hamza Salih
    PROCEEDINGS OF THE 2017 SIXTEENTH IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS ITHERM 2017, 2017, : 968 - 976
  • [37] Energy saving potential analysis of two-phase immersion cooling system with multi-mode condenser
    Zhang, Ce
    Sun, Xiaoqing
    Han, Zongwei
    Li, Xiuming
    Dong, Jiaxiang
    APPLIED THERMAL ENGINEERING, 2023, 219
  • [38] Energy-saving optimal control of secondary district cooling system based on tribal intelligent evolution optimization algorithm
    Hong, Xiaoxi
    Yao, Ye
    Wang, Kui
    Yang, Jianzhong
    Liu, Qimei
    ENERGY, 2025, 316
  • [39] Comparative study on different energy-saving plans using water-side economizer to retrofit the computer room air conditioning system
    Zou, Sikai
    Zhang, Quan
    Yue, Chang
    JOURNAL OF BUILDING ENGINEERING, 2023, 69
  • [40] High-efficiency and energy-saving control strategy for the water-circulating solar energy system in the greenhouse
    Weiwei X.
    Chengwei M.
    Hao S.
    Yiwei L.
    Ruifeng C.
    Yi Z.
    Nongye Gongcheng Xuebao/Transactions of the Chinese Society of Agricultural Engineering, 2022, 38 (22): : 149 - 157