Power Quality Improvement with Three-Phase Shunt Active Power Filter Prototype Based on Harmonic Component Separation Method with Low-Pass Filter

被引:0
作者
Gaiceanu, Marian [1 ]
Epure, Silviu [1 ]
Solea, Razvan Constantin [1 ]
Buhosu, Razvan [1 ]
机构
[1] Dunarea Jos Univ Galati, Fac Automat Comp Elect Engn & Elect, Galati 800008, Romania
关键词
shunt active power filter; prototype; compensation strategy; harmonic component separation method; low-pass filter; energy efficiency; sustainability; THDu; THDi;
D O I
10.3390/en18030556
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This work contributes to both Romania's and the European Union's energy policies by highlighting the research results obtained within the Dunarea de Jos University of Galati, but also through the technological transfer of this knowledge to the industry. In order to improve the power quality of the nonlinear loads connected to the electrical grid, a three-phase shunt active power filter prototype based on the Harmonic Component Separation Method with a Low-Pass Filter was used. The active power filter is connected at the Point of Common Coupling to compensate for individual loads or even all of them simultaneously. Therefore, active power filters can be used to compensate for the power factor and reduce the harmonic distortion of power supplies, or for processes subsequently connected to additional nonlinear loads, thus improving the energy efficiency. The shunt active power filter prototype is composed of the power side (three-phase insulated gate bipolar transistor bridge, DC link capacitor precharge system, inductive filter) and the control side (gate drive circuits, control subsystems, signal acquisition system). The filter control strategy is based on the principle of separating harmonic components with a low-pass filter, implemented by the authors on the industrial prototype. In this paper, the main technical features of the industrial shunt active power filter prototype are specified. The authors of this paper involved three cascaded control loops: the DC link voltage control loop, the shunt active power filter current control loop and the phase-locked loop. Both simulation and experimental results for the shunt-type active power filter prototype were obtained. By analyzing the obtained waveforms of the power supply source in two cases (with and without an active power filter), a decrease in the total harmonic distortion was demonstrated, both the voltage harmonic distortion factor THDu and the current harmonic distortion factor THDi in the case of the active power filter connection. By using the Field-Programmed Gate Array processing platform, the powerful computational speed features were exploited to implement the active shunt power filter control on an experimental test bench. Conducting source current harmonics mitigation increased the efficiency of the power system by decreasing the respective harmonic Joule losses. The energy-saving feature led to the increased added value of the parallel active power filter. Through the performed laboratory tests, the authors demonstrated the feasibility of the proposed control solution for the industrial prototype. In accordance with the European Union's Research and Technological Development Policy, the development of an innovation ecosystem was taken into consideration. The unified and efficient integration of all the specific actors (enterprises, research institutes, universities and entrepreneurs) in innovation was achieved.
引用
收藏
页数:20
相关论文
共 32 条
  • [1] Enhancing Doubly Fed Induction Generator Low-Voltage Ride-through Capability Using Dynamic Voltage Restorer with Adaptive Noise Cancellation Technique
    Ahmed, Mohamed Adel
    Kandil, Tarek
    Ahmed, Emad M.
    [J]. SUSTAINABILITY, 2022, 14 (02)
  • [2] Akagi H, 1995, PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS FOR INDUSTRIAL GROWTH, VOLS I & II, P417, DOI 10.1109/PEDES.1996.539652
  • [3] Mathematical Modeling and Analysis of Capacitor Voltage Balancing for Power Converters with Fewer Switches
    Alghaythi, Mamdouh L.
    Irudayaraj, Gerald Christopher Raj
    Ramu, Senthil Kumar
    Govindaraj, Praveenraj
    Vairavasundaram, Indragandhi
    [J]. SUSTAINABILITY, 2023, 15 (13)
  • [4] A Robust Dynamic Control Strategy for Standalone PV System under Variable Load and Environmental Conditions
    Anjum, Waqas
    Husain, Abdul Rashid
    Aziz, Junaidi Abdul
    Rehman, Syed Muhammad Fasih Ur
    Bakht, Muhammad Paend
    Alqaraghuli, Hasan
    [J]. SUSTAINABILITY, 2022, 14 (08)
  • [5] [Anonymous], 2019, Electromagnetic Compatibility (EMC)Part 6-2: Generic StandardsImmunity Standard for Industrial Environments
  • [6] [Anonymous], 1997, Electronic Equipment for Use in Power Installations
  • [7] [Anonymous], 2019, Electromagnetic Compatibility (EMC)Part 6-4: Generic StandardsEmission Standard for Industrial Environments
  • [8] AN ADAPTIVE HYSTERESIS-BAND CURRENT CONTROL TECHNIQUE OF A VOLTAGE-FED PWM INVERTER FOR MACHINE DRIVE SYSTEM
    BOSE, BK
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1990, 37 (05) : 402 - 408
  • [9] Analysis and Optimization of Output Low-Pass Filter for Current-Source Single-Phase Grid-Connected PV Inverters
    Ertasgin, Gurhan
    Whaley, David M.
    [J]. APPLIED SCIENCES-BASEL, 2024, 14 (22):
  • [10] Gupta N., 2011, International Journal of Engineering, Science and Technology, V3, P236, DOI DOI 10.4314/IJEST.V3I4.68556