Optimization of optimal discharge pressure for a novel solar-assisted ejector subcooling CO2 transcritical refrigeration system based on NSGA-II

被引:0
作者
Yin, Tailan [1 ]
Yang, Qichao [1 ]
Jiang, Jiawei [1 ]
Zhao, Yuanyang [1 ]
Liu, Guangbing [1 ]
Li, Liansheng [1 ]
机构
[1] Qingdao Univ Sci & Technol, Coll Electromech Engn, Qingdao 266061, Peoples R China
基金
中国国家自然科学基金;
关键词
Ejector refrigeration; Transcritical CO2 refrigeration; Optimal discharge pressure; Multi-objective optimization; NSGA-II; PUMP WATER-HEATER; MULTIOBJECTIVE OPTIMIZATION; EXERGY ANALYSIS; THERMODYNAMIC ANALYSIS; PERFORMANCE EVALUATION; CARBON-DIOXIDE; 3E ANALYSES; CYCLES; ENERGY; TOPSIS;
D O I
10.1016/j.applthermaleng.2025.125574
中图分类号
O414.1 [热力学];
学科分类号
摘要
In recent years, due to the increasing energy consumption of buildings, energy saving and emission reduction have become the focus of attention in the field of refrigeration and air conditioning. This research proposes a novel system for the field of solar air conditioning: a solar-drive ejector subcooling CO2 transcritical refrigeration system (SESRS). The SESRS system both utilizes renewable solar energy and improves the energy efficiency of the system. This novel cascade cycle can effectively increase the COP of the system. But thermodynamic analysis using the Popt,dis reveals that although the COP of the system reaches the maximum value, the Asc also reaches the maximum value, and there is a problem of poor system economics. Therefore, in this study, a Non-dominated Sorting Genetic Algorithm-II (NSGA-II) is used for multi-objective optimization of conflicting objectives COP and Asc. When Ta is 35 degrees C, the optimized discharge pressure (Pdis,optimized) obtained by thermodynamic calculation gives a COP of 2.19 and Asc of 8 m2. Although the COP is 12.34 % lower than that obtained after using the optimal discharge pressure (Popt,SESRS) calculation, the Asc is reduced by 65.57 %.When discharge pressures are adopted in terms of Pdis,optimized and Popt,TCRS, the performance and economy of the two discharge pressure calculations are closer. This multi-objective optimization approach considers both the coefficient of performance and the economics of SESRS, and integrating these criteria into the optimization process results in an environmentally friendly and economically viable SESRS cycle.
引用
收藏
页数:15
相关论文
共 61 条
  • [1] A solar ejector cooling system using refrigerant R134a in the Athens area
    Alexis, GK
    Karayiannis, EK
    [J]. RENEWABLE ENERGY, 2005, 30 (09) : 1457 - 1469
  • [2] Exergetic, economic and environmental (3E) analyses, and multiobjective optimization of a CO2/NH3 cascade refrigeration system
    Aminyavari, Mehdi
    Najafi, Behzad
    Shirazi, Alec
    Rinaldi, Fabio
    [J]. APPLIED THERMAL ENGINEERING, 2014, 65 (1-2) : 42 - 50
  • [3] Performance Analysis of an Ejector Enhanced Two-Stage Auto-Cascade Refrigeration Cycle for Low Temperature Freezer
    Bai, Tao
    Lu, Yu
    Yan, Gang
    Yu, Jianlin
    [J]. JOURNAL OF THERMAL SCIENCE, 2021, 30 (06) : 2015 - 2026
  • [4] Optimum design of a solar ejector refrigeration system for various operating scenarios
    Bellos, Evangelos
    Tzivanidis, Christos
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2017, 154 : 11 - 24
  • [5] An improved cascade mechanical compression-ejector cooling cycle
    Chen, Guangming
    Ierin, Volodymyr
    Volovyk, Oleksii
    Shestopalov, Kostyantyn
    [J]. ENERGY, 2019, 170 : 459 - 470
  • [6] Energy and exergy analysis of a new direct-expansion solar assisted vapor injection heat pump cycle with subcooler for water heater
    Chen, Jiaheng
    Yu, Jianlin
    [J]. SOLAR ENERGY, 2018, 171 : 613 - 620
  • [7] A review on versatile ejector applications in refrigeration systems
    Chen, Jianyong
    Jarall, Sad
    Havtun, Hans
    Palm, Bjorn
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 49 : 67 - 90
  • [8] Investigation of ejectors in refrigeration system: Optimum performance evaluation and ejector area ratios perspectives
    Chen, Jianyong
    Havtun, Hans
    Palm, Bjorn
    [J]. APPLIED THERMAL ENGINEERING, 2014, 64 (1-2) : 182 - 191
  • [9] Thermodynamic analysis of a novel solar-driven booster-assisted ejector refrigeration cycle
    Cheng, Yue
    Wang, Min
    Yu, Jianlin
    [J]. SOLAR ENERGY, 2021, 218 : 85 - 94
  • [10] Energy, exergy, and economic (3E) analyses and multi-objective optimization of a cascade absorption refrigeration system for low-grade waste heat recovery
    Cui, Peizhe
    Yu, Mengxiao
    Liu, Zhiqiang
    Zhu, Zhaoyou
    Yang, Sheng
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2019, 184 : 249 - 261