An experimental study on the suppression of shielded fires by water mist sprays in a compartment

被引:0
|
作者
Moinuddin, Khalid [1 ]
Mahmud, H. M. Iqbal [1 ,2 ]
Joseph, Paul [1 ]
Gamble, Grant [3 ]
Suendermann, Brigitta [3 ]
Wilkinson, Cameron [4 ]
Bossard, James [4 ]
机构
[1] Victoria Univ, Inst Sustainable Ind & Liveable Cities, Melbourne, Vic 3030, Australia
[2] Khulna Univ Engn & Technol, Dept Civil Engn, Khulna, Bangladesh
[3] Def Sci & Technol Grp, Platforms Div, Melbourne, Vic 3207, Australia
[4] BAE Syst, Adelaide, Australia
关键词
ISO; 9705; room; Pool fire; Shielding; Heat release rate; Water mist; Suppression; HEAT RELEASE; ENCLOSURE; MODEL;
D O I
10.1016/j.firesaf.2025.104339
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study investigates the effectiveness of water mist systems in extinguishing shielded fires aboard marine vessels. Experiments were conducted in a standard ISO 9705 room, modified to simulate a scaled-down version of a ship engine room. A series of ten benchmark experiments were conducted varying the size of the fuel tray, ventilation in the room, presence of obstruction and its size, and suppression of the fire. Heptane was used as fuel and water mist nozzles were employed for fire suppression. The heat release rate, temperature, thermal radiation and oxygen concentration were measured during the experiments. The results showed that the water mist spray of 22 lpm extinguished a reasonably large fire of 570 kW quickly, even when the fire was shielded with a 1.4 x 1.4 m obstruction. After activation of the spray the concentration of oxygen also reduced to below combustion requirements. Key findings highlight the capability of water mist in suppressing shielded fires effectively, despite the complexities introduced by obstructions. The water mist showed an outstanding ability to reduce heat release rate, lower radiation and temperature levels, and decrease oxygen concentrations to below combustible levels, effectively extinguishing fires in compliance with established pass/fail criteria for maritime fire suppression. The data of these experiments can serve as a benchmark for validating numerical and analytical fire models.
引用
收藏
页数:18
相关论文
共 50 条
  • [1] Experimental study on the mitigation of backdraft in compartment fires with water mist
    Weng, WG
    Fan, WC
    JOURNAL OF FIRE SCIENCES, 2002, 20 (04) : 259 - 278
  • [2] A numerical study of water-mist suppression of large scale compartment fires
    Prasad, K
    Patnaik, G
    Kailasanath, K
    FIRE SAFETY JOURNAL, 2002, 37 (06) : 569 - 589
  • [3] Simulation Study on Suppressing Shielded Fires by Water Mist Systems
    Hamzehpour, Azad
    Verda, Vittorio
    Borchiellini, Romano
    FIRE-SWITZERLAND, 2023, 6 (04):
  • [4] Suppression effectiveness of water-mist sprays on accelerated wood-crib fires
    Santangelo, Paolo E.
    Jacobs, Bryson C.
    Ren, Ning
    Sheffel, Joshua A.
    Corn, May L.
    Marshall, Andre W.
    FIRE SAFETY JOURNAL, 2014, 70 : 98 - 111
  • [5] Experimental and Numerical Study of Water Mist Fire Suppression System Effectiveness on Shielded Fire
    Kuswantoro
    Nugroho, Y. S.
    3RD INTERNATIONAL TROPICAL RENEWABLE ENERGY CONFERENCE SUSTAINABLE DEVELOPMENT OF TROPICAL RENEWABLE ENERGY (I-TREC 2018), 2018, 67
  • [6] FIRE SUPPRESSION BY WATER-MIST SPRAYS: EXPERIMENTAL AND NUMERICAL ANALYSIS
    Santangelo, Paolo E.
    Tartarini, Paolo
    Pulvirenti, Beatrice
    Valdiserri, Paolo
    Marshall, Andre W.
    PROCEEDINGS OF THE ASME INTERNATIONAL HEAT TRANSFER CONFERENCE - 2010, VOL 5: FUEL CELLS, GAS TURBINES, HEAT PIPES, JET IMPINGEMENT, RADIATION, 2010, : 571 - 580
  • [7] Experimental and Numerical Study on Fire Suppression via Water Mist in a Mechanically Ventilated Compartment
    Acherar, Lahna
    Wang, Hui-Ying
    Coudour, Bruno
    Garo, Jean Pierre
    4TH EUROPEAN SYMPOSIUM ON FIRE SAFETY SCIENCE, 2024, 2885
  • [8] Experimental Studies on Water Mist Suppression of Liquid Fires with and without Additives
    Cong, Beihua
    Liao, Guangxuan
    JOURNAL OF FIRE SCIENCES, 2009, 27 (02) : 101 - 123
  • [9] Study on numerical simulation of water mist suppression in tunnel fires
    Zhu Wei
    Wang Tong
    You Fei
    Jin Longzhe
    PROGRESS IN MINING SCIENCE AND SAFETY TECHNOLOGY, PTS A AND B, 2007, : 1884 - 1889
  • [10] Experimental study of extinguishing shielded fires by a low-pressure multi-orifice water mist nozzle
    Hamzehpour, Azad
    Verda, Vittorio
    Borchiellini, Romano
    FIRE SAFETY JOURNAL, 2024, 146