Research on Diagnostic Methods for Zero-Value Insulators in 110 kV Transmission Lines Based on Spatial Distribution Characteristics of Electric Fields

被引:0
|
作者
Zheng, Lei [1 ,2 ]
Yin, Pengxiang [1 ,2 ]
Li, Jian [1 ,2 ]
Liu, Hui [3 ]
Li, Tao [1 ,2 ]
Luo, Hao [1 ,2 ]
机构
[1] NARI Grp Corp Ltd, Nanjing 211106, Peoples R China
[2] Wuhan NARI Ltd Liabil Co, State Grid Elect Power Res Inst, Wuhan 430206, Peoples R China
[3] Grid Shandong Elect Power Res Inst, Jinan 250003, Peoples R China
关键词
zero-value insulators; electric field distortion; finite element simulation; electric field distribution; MLP neural network algorithm;
D O I
10.3390/en18061534
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Porcelain insulators in power systems are subject to prolonged mechanical and electrical loads, as well as environmental factors such as climate variations. These conditions often lead to degradation of insulation performance and structural damage, resulting in a decrease in insulation resistance and the formation of cracks, which in turn produce "zero-value" insulators. The presence of zero-value insulators significantly increases the risk of pollution flashovers and electrical arcing, with flashover occurrences possible even under normal operating voltages. This poses a severe threat to the safe and stable operation of the power grid. This study develops a high-fidelity simulation model of insulator strings containing zero-value defects for a 110 kV transmission line. The impact of variations in the position and quantity of zero-value insulators on the spatial electric field distribution is analyzed in detail. Based on the electric field changes, a detection method for zero-value insulators is proposed. Additionally, a prediction model for the electric field strength of insulators with zero-value defects is developed using a Multilayer Perceptron (MLP) neural network. A spatial electric field distribution database for insulator strings containing zero-value defects is also established. The accuracy of the model is validated through laboratory testing.
引用
收藏
页数:14
相关论文
共 14 条
  • [1] Influence of Deteriorated Porcelain Insulator on Electric Field and Potential Distribution of Insulators Strings in 110kV Transmission Lines
    Xu Changfu
    Hu Chengbo
    Xu Jiayuan
    Liu Yunpeng
    Zhang Kaiyuan
    Pei Shaotong
    2017 IEEE INTERNATIONAL CONFERENCE ON SMART GRID AND SMART CITIES (ICSGSC), 2017, : 162 - 166
  • [2] Research on zero-value insulator detection method based on infrared imaging characteristics
    College of Electrical Engineering & New Energy, China Three Gorges University, 8 University Road, Hubei, Yichang
    443002, China
    不详
    不详
    810000, China
    Proc SPIE Int Soc Opt Eng, 1600,
  • [3] Identification of Deteriorated Porcelain Insulators for Transmission Lines Based on Electric Field Distribution Measurement Method
    Zheng, Weigang
    Ma, Yiling
    Geng, Lina
    Zhang, Zhongrui
    Tang, Hong
    Fan, Qirui
    JOURNAL OF ELECTRONIC MATERIALS, 2025,
  • [4] Live-Line Detection of Deteriorated Insulators on Overhead Transmission Lines Based on Electric Field Distribution
    Wu, Shaocheng
    Wang, Linong
    Song, Bin
    Gao, Jiachen
    IEEE SENSORS JOURNAL, 2024, 24 (02) : 1687 - 1695
  • [5] Electric Field Distribution Calculation and Analysis of Composite Insulators Operating on Double Circuit Transposition Tower in 500kV Transmission Lines
    Guo, Chenjun
    Liu, Lishuai
    Yu, Hong
    Ma, Yi
    Mei, Hongwei
    Wang, Liming
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 486 - 489
  • [6] Control of an inspection robot for 110KV power transmission lines based on expert system design methods
    Zhou, FY
    Wang, JD
    Li, YB
    Wang, J
    Xiao, HR
    2005 IEEE INTERNATIONAL CONFERENCE ON CONTROL APPLICATIONS (CCA), VOLS 1AND 2, 2005, : 1563 - 1568
  • [7] Electric field distribution and voltage-sharing characteristics of composite tower in 330 kV double circuit transmission lines
    Wang, Qingyu
    Wang, Haoran
    Yang, Xi
    Wang, Jialong
    Peng, Zongren
    Dianwang Jishu/Power System Technology, 2015, 39 (12): : 3649 - 3655
  • [8] Research on simulation and detection of space electric field distribution of deteriorated insulators in three-phase over-head transmission lines
    Jia, Jun
    Wang, Maofei
    Dai, Yongdong
    Zhang, Haoling
    Gao, Song
    Wang, Shenyu
    JOURNAL OF COMPUTATIONAL METHODS IN SCIENCES AND ENGINEERING, 2023, 23 (03) : 1451 - 1466
  • [9] Sheds configuration optimization of AC composite insulators used in AC transmission lines at icing areas based on electric field distribution
    Jiang, Xingliang
    Liu, Yu
    Zhang, Zhijin
    Hu, Jianlin
    Yin, Fanghui
    Xiang, Ze
    Gaodianya Jishu/High Voltage Engineering, 2013, 39 (01): : 210 - 217
  • [10] Research on Electric Field Distribution and Protection Technology of Live line Workers on ±500kV Flexible DC Transmission Lines
    Wu, Tian
    Liu, Shiqi
    Lu, Jun
    Li, Benliang
    2019 4TH INTERNATIONAL CONFERENCE ON INTELLIGENT GREEN BUILDING AND SMART GRID (IGBSG 2019), 2019, : 250 - 259