Optimized method for testing equipment sensitivity to voltage sags and interruptions based on DC link voltage prediction

被引:0
作者
Yao, Jieyu [1 ]
Lv, Wenxuan [1 ,2 ]
Li, Ning [1 ]
Jiang, Tiantao [1 ,3 ]
机构
[1] Univ Edinburgh, Edinburgh EH9 3FB, Scotland
[2] North China Elect Power Univ, Beijing 102206, Peoples R China
[3] Heriot Watt Univ, Edinburgh EH14 4AS, Scotland
关键词
Dc link voltage prediction; Diode bridge rectifier; Equipment sensitivity test; Malfunction prediction; Power quality; Voltage sag and interruption; SEVERITY; MODEL;
D O I
10.1016/j.epsr.2024.111337
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Determining equipment sensitivity and tolerance curves for voltage sags is essential for identifying vulnerable equipment and planning preventive maintenance. However, existing test procedures are repetitive and laborintensive. To address this, this paper proposes a method to automatically predict equipment malfunction and reconstruct tolerance curves specifically for voltage sags and short interruptions, based on DC link voltage prediction. First, extensive sensitivity testing was conducted using existing testing methods to understand equipment behavior and establish malfunction criteria for voltage sags. The probabilistic range of tolerance curves was obtained by considering a wide range of sag scenarios. Equipment malfunction was observed when the minimum voltage across the DC link capacitor fell below the required operational level. Based on this established malfunction criteria, an optimized method was proposed, which requires only a few known nameplate parameters and a few initial tests. It achieves high prediction accuracy for DC link voltage across all cases (with an R-squared value of up to 1 and a mean absolute percentage error of <5 %). Additionally, the reconstructed tolerance curves obtained by the proposed method closely align with the measured tolerance curves, validating the effectiveness of the proposed method.
引用
收藏
页数:11
相关论文
共 31 条
[1]  
Akolkar S. M., 2010, 2010 9th International Power & Energy Conference (IPEC 2010), P957, DOI 10.1109/IPECON.2010.5696951
[2]  
[Anonymous], 2010, BS EN IEC 61000-4-17
[3]  
[Anonymous], 2020, BS EN IEC 61000-4-11
[4]  
[Anonymous], 2021, BS EN IEC 61000-3-2
[5]   Mathematical functions for the analysis of luminescence decays with underlying distributions 1. Kohlrausch decay function (stretched exponential) [J].
Berberan-Santos, MN ;
Bodunov, EN ;
Valeur, B .
CHEMICAL PHYSICS, 2005, 315 (1-2) :171-182
[6]   A Study on Voltage Sag Assessment for Multiple Sensitive Loads Based on Probabilistic Prediction [J].
Chae, Hakyung ;
Park, Chang-Hyun .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2023, 18 (03) :2395-2405
[7]  
Chan JY, 2007, IEEE POWER ENG SOC, P737
[8]   A novel methodology for determining the voltage sag Impact Factor [J].
Costa, Marcos V. ;
Filho, Jose M. C. ;
Leborgne, Roberto C. ;
Pereira, Natanael B. .
ELECTRIC POWER SYSTEMS RESEARCH, 2019, 174
[9]  
Djokic SZ, 2005, IEEE T POWER DELIVER, V20, P494, DOI 10.1109/TPWRD.2004.832353
[10]   Sensitivity of personal computers to voltage sags and short interruptions [J].
Djokic, SZ ;
Desmet, J ;
Vanalme, G ;
Milanovic, JV ;
Stockman, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :375-383