Study on the Characteristics of Turn-to-Turn Short Circuit Faults in the Primary Windings of the Generator Terminal Voltage Transformer

被引:0
|
作者
Wei, Yang [1 ]
Wu, Ligui [1 ]
Li, Guangyao [1 ]
Li, Chen [1 ]
Sun, Yue [1 ]
Qiu, Pengyu [2 ]
Qian, Yuzhe [2 ]
Chen, Jun [2 ]
机构
[1] China Yangtze Power Co Ltd, Three Gorges Hydropower Plant, Yichang 443133, Peoples R China
[2] Nanjing Tech Univ, Coll Elect Engn & Control Sci, Nanjing 211816, Peoples R China
来源
ELECTRONICS | 2024年 / 13卷 / 23期
关键词
voltage transformer; turn-to-turn short circuit; Altair Flux 3D; fault characteristics; magnetic field analysis; STRATEGY;
D O I
10.3390/electronics13234772
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Turn-to-turn short circuit faults in the primary winding of generator terminal voltage transformers can lead to erroneous operation of stator grounding protection systems. This paper analyzes the fault characteristics associated with such failures and derives formulas for the fault phase current and zero-sequence voltage during a turn-to-turn short circuit in the primary winding. A 3D finite element model of the generator terminal voltage transformer is established by using Altair Flux 3D, and the accuracy of the model is verified. Based on this model, simulation tests were conducted to investigate turn-to-turn short circuits in the primary winding. The results reveal that as the number of shorted turns increases, the voltage of the fault phase decreases continuously while the voltages of the other two phases increase. The current in the short-circuited phase rises significantly, accompanied by an increase in zero-sequence voltage. Visualizations of magnetic field parameters indicate that as the number of shorted turns increases, the magnetic induction magnitude of the fault phase rises steadily and approaches saturation, resulting in heightened magnetic field intensity near the shorted turns. This analysis of fault characteristics through simulation contributes to the advancement of fault diagnosis systems for generator terminal voltage transformers.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] Transformer Terminal-Duality Model for Windings Turn-to-Turn Faults Simulation
    Farzin, Nima
    Vakilian, Mehdi
    Hajipour, Ehsan
    2020 14TH INTERNATIONAL CONFERENCE ON PROTECTION AND AUTOMATION OF POWER SYSTEMS (IPAPS), 2020, : 71 - 76
  • [2] On-line diagnosis for turn-to-turn short circuit of rotor windings in turbo generator
    Li, Yonggang
    Li, Heming
    Dianli Xitong Zidonghue/Automation of Electric Power Systems, 2003, 26 (20): : 47 - 49
  • [3] Study on Methodology Detecting Turn-to-turn Short Circuit of Transformer
    Quan, Yusheng
    Zhao, Xin
    Chen, Guang
    Zhou, Enze
    ENERGY AND POWER TECHNOLOGY, PTS 1 AND 2, 2013, 805-806 : 876 - +
  • [4] Analysis on unbalanced magnetic pull generated by turn-to-turn short circuit of rotor windings within turbine generator
    Wu, Yu-Cai
    Li, Yong-Gang
    Feng, Wen-Zong
    Zhang, Wen-Jing
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2015, 19 (03): : 37 - 44
  • [5] Analysis on Leakage Flux Characteristics of Turn-to-Turn Short-circuit Fault for Power Transformer
    Zheng, Yuping
    Gong, Xinyi
    Pan, Shuyan
    Sun, Jiahao
    Deng, Jinzhao
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2022, 46 (15): : 121 - 127
  • [6] Improved Brushless Synchronous Generator Model to Study the Turn-to-Turn Short Circuit Fault
    Sivakumar, Nadarajan
    Bhangu, Bicky
    Panda, S. K.
    Gupta, Amit Kumar
    2014 IEEE PES GENERAL MEETING - CONFERENCE & EXPOSITION, 2014,
  • [7] Transformer Protection Against Turn-To-Turn Faults.
    Gagen, A.F.
    Komissarov, G.A.
    Chechushkov, G.A.
    Elektrichestvo, 1974, (02): : 56 - 59
  • [8] Anti-Interference and Location Performance for Turn-to-Turn Short Circuit Detection in Turbo-Generator Rotor Windings
    Wu, Yucai
    Ma, Guanhua
    ENERGIES, 2019, 12 (07)
  • [9] Comprehensive Modeling and Analysis of Stator Turn-to-Turn Short-Circuit Faults in a DFIG
    Yan, Chenguang
    Wang, Weixiang
    Liu, Qinzhi
    Liu, Zhangheng
    Shu, Jin
    Zhao, Jikai
    Zhang, Baohui
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2024, 34 (08)
  • [10] Early Detection of Turn-to-Turn Faults in Power Transformer Winding: An Experimental Study
    Moradzadeh, Arash
    Pourhossein, Kazem
    2019 INTERNATIONAL AEGEAN CONFERENCE ON ELECTRICAL MACHINES AND POWER ELECTRONICS (ACEMP) & 2019 INTERNATIONAL CONFERENCE ON OPTIMIZATION OF ELECTRICAL AND ELECTRONIC EQUIPMENT (OPTIM), 2019, : 199 - 204