Real Time Fractional Robust Adaptive Scheme for Frequency Regulation in Double Area Hybrid Power System With Renewables

被引:0
作者
Ragab, Ahmed [1 ]
Allam, Dalia [2 ]
Zobaa, Ahmed F. [3 ]
Attia, Hazem Ali [1 ]
机构
[1] Fayoum Univ, Fac Engn, Engn Math & Phys Dept, Faiyum 63514, Egypt
[2] Fayoum Univ, Fac Engn, Elect Engn Dept, Faiyum 63514, Egypt
[3] Brunel Univ London, Coll Engn Design & Phys Sci, Uxbridge UB8 3PH, England
来源
IEEE ACCESS | 2025年 / 13卷
关键词
Frequency control; Power system stability; Control systems; Load modeling; Adaptation models; Wind energy; Regulators; Renewable energy sources; Uncertainty; Wind farms; Adaptive model reference control; disturbance rejection; fractional control; frequency regulation; renewable resources; MODEL-PREDICTIVE CONTROL; ORDER PID CONTROLLER; LOAD-FREQUENCY; IMPLEMENTATION; STABILITY; DESIGN;
D O I
10.1109/ACCESS.2025.3525999
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Load frequency regulation in hybrid grid is a very crucial issue. This work introduces robust-adaptive control methodology to provide accurate response against any disturbances. Control scheme of two main parts has been introduced. The first one is a novel fractional order model reference adaptive controller where fractional calculus merits and e-modification robust algorithm have been merged with the adaptive skills creating the fractional order model reference robust-adaptive controller. This robust-adaptive controller has utilized output feedback approach that requires only the output state without detailed system model information. The fractional orders have been optimized using a nature-inspired algorithm named Artificial Rabbits. The second part of the control scheme is a disturbance rejection observer that is able to estimate and eliminate external and internal disturbances. For fair comparison, results of the proposed scheme have been compared to that of the most efficient controllers obtained from the literature named fractional order proportional integral derivative controller and integral controller. Furthermore, the integer version of the proposed controller has been tested and compared with the proposed controller to prove the robustness of the fractional modification. To validate the superiority of the proposed controller, five challenging scenarios have been considered, encompassing load fluctuations, integration of renewable energy sources, changes in system parameters and time delay attacks. The proposed controller effectively minimizes area control error achieving stability and showing cost function enhancement of 15% to 152% compared to other tested controllers in all scenarios. Thus, it is strongly recommended for load frequency regulation in multi-area power systems.
引用
收藏
页码:5056 / 5075
页数:20
相关论文
共 64 条
  • [11] Bat inspired algorithm based optimal design of model predictive load frequency control
    Elsisi, M.
    Soliman, M.
    Aboelela, M. A. S.
    Mansour, W.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 83 : 426 - 433
  • [12] Fan L., 2017, CONTROL DYNAMICS POW
  • [13] Garnier H, 2008, ADV IND CONTROL, P1, DOI 10.1007/978-1-84800-161-9
  • [14] Disturbance observer aided optimised fractional-order three-degree-of-freedom tilt-integral-derivative controller for load frequency control of power systems
    Guha, Dipayan
    Roy, Provas Kumar
    Banerjee, Subrata
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2021, 15 (04) : 716 - 736
  • [15] L1 Adaptive Control for Safety-Critical Systems GUARANTEED ROBUSTNESS WITH FAST ADAPTATION
    Hovakimyan, Naira
    Cao, Chengyu
    Kharisov, Evgeny
    Xargay, Enric
    Gregory, Irene M.
    [J]. IEEE CONTROL SYSTEMS MAGAZINE, 2011, 31 (05): : 54 - 104
  • [16] Implementation of a DSP-controlled photovoltaic system with peak power tracking
    Hua, CC
    Lin, JG
    Shen, CM
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1998, 45 (01) : 99 - 107
  • [17] Janssens N, 1999, IEEE POWER ENGINEERING SOCIETY - 1999 WINTER MEETING, VOLS 1 AND 2, P554, DOI 10.1109/PESW.1999.747514
  • [18] Neural predictive controller of a two-area load frequency control for interconnected power system
    Kassem, Ahmed M.
    [J]. AIN SHAMS ENGINEERING JOURNAL, 2010, 1 (01) : 49 - 58
  • [19] Kaufman H., 2012, DIRECT ADAPTIVE CONT
  • [20] Kouba NEY, 2015, 2015 IEEE INTERNATIONAL CONFERENCE ON SMART ENERGY GRID ENGINEERING (SEGE 2015)