Experimental analysis of combustion intensity of irregular multiple pool fires based on the characteristics of flame merging, flame height, and mass loss rate

被引:2
|
作者
Shi, Yangjin [1 ]
Li, Bo [1 ]
Wu, Gexin [1 ]
Lu, Kaihua [1 ]
Hu, Fan [1 ]
机构
[1] China Univ Geosci, Fac Engn, LuMo Rd 388, Wuhan 430074, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
Industrial thermal safety management; Multiple pool fires; Flame merging; Flame height; Mass loss rate; Fire interaction; TURBULENT-DIFFUSION FLAMES; BURNING RATE; THERMAL-RADIATION; HEAT FEEDBACK; EVOLUTION; SIZE;
D O I
10.1016/j.fuel.2024.133045
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Multiple pool fires, a typical scenario of industrial thermal disasters, often occur in chemical fuel storage areas. To guide the industrial thermal safety management, the irregular multiple square pool fire experiments (side length d) with varying conditions of pool source pitches p (0-60 cm), pool numbers n (1-4), and layout patterns (linear-arranged, square-arranged) are conducted. The characteristic behaviors of the flame merging, the flame height, and the fuel mass loss rate are examined. The results include: an average flame merging probability P-m,P-a is proposed to quantify the merging intensity among irregular multiple pool fires, which exhibits a linear relationship with the ratio of pool source pitch to the multi-flame height at zero pitch p/H-p=0. Then, a predictive model is developed for the flame height, correlating it with the group parameter p(2)+nd(2)n / (p(2)+d(2)). A dimensionless average mass loss rate m(t)(& lowast;) is introduced to characterize the impact of interaction intensity on the global combustion of multiple fires. Due to the competitive effects of two dominant mechanisms, m(t)(& lowast; )initially increases and then decreases as the fuel surface area ratio r increases. Furthermore, under the dominant mechanism of radiative heat feedback and air entrainment, two change processes are observed in m(t)(& lowast;): a slow increase followed by a rapid rise. Within the experimental ranges, in non-zero pool source pitch scenarios, m(t)(& lowast;) is greater in the square-arranged configuration compared to m(t)(& lowast;) in the linear layout. The comprehensive impact coefficient A(i) is then employed to explore the influence of interaction strength on the individual fire sources. Overall, A(i) of the central fire exceeds that of the side fire. Additionally, the nondimensional parameter alpha is defined to reveal the extent of the impact of pool source pitch, pool number, and layout pattern on A(i). The influence of pool number and layout pattern on A(i) is relatively minor, with pool source pitch being dominant. Finally, based on the energy conservation principle, the heat transfer equation, and the solid flame model, a correlation for the mass loss rate of any pool in multiple fire sources is established. The above correlations are validated using the results of previous research, demonstrating their applicability and reliability.
引用
收藏
页数:15
相关论文
共 41 条
  • [11] An experimental investigation of flame height and air entrainment rate of double jet fires
    Wang, Kai
    Tao, Changfa
    Liu, Qin
    Qian, Yejian
    He, Peixiang
    EXPERIMENTAL HEAT TRANSFER, 2018, 31 (01) : 22 - 31
  • [12] Study on the evolution of flame morphology and burning rate of pool fires under the combined influence of crosswind and ullage height
    Zhang, Shaohua
    Zhao, Jinlong
    Hu, Zhenqi
    Zhang, Jianping
    Jiang, Huiling
    ENERGY, 2025, 322
  • [13] Scaling flame height of fully turbulent pool fires based on the turbulent transport properties
    Lei, Jiao
    Liu, Naian
    PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2017, 36 (02) : 3139 - 3148
  • [14] Experimental study on flame merging probability and pulsation frequency of annular hydrocarbon pool fires with various inner and outer diameters
    Deng, Lei
    Tang, Fei
    Ma, Xin
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2021, 146 : 473 - 480
  • [15] Experimental study on the flame merging and temperature profile produced by two pool fires beneath the curved ceiling
    Li, Linjie
    Nen, Tianjiao
    Wu, Zhaoguo
    Huang, Huixian
    Zhang, Haibing
    Sun, Yonggan
    Gao, Zihe
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 60
  • [16] Effects of wind speed, spacing distance and heat release rate on the combustion and flame merging characteristics of two extra-thin line fires
    Huang, Xinjie
    Ding, Hailong
    Zhang, Xinyi
    Li, Xinyi
    Wang, Miaomiao
    Zhang, Pengyuan
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 60
  • [17] Experimental study on the flame performance and burning characteristics of two unequal rectangular pool fires
    Li, Bo
    Wu, Gexin
    Shi, Yangjin
    Xie, Yujie
    Mao, Shaohua
    FUEL, 2024, 369
  • [18] Experimental study of tunnel sidewall effect on flame characteristics and air entrainment factor of methanol pool fires
    Gao, Z. H.
    Liu, Z. X.
    Ji, J.
    Fan, C. G.
    Li, L. J.
    Sun, J. H.
    APPLIED THERMAL ENGINEERING, 2016, 102 : 1314 - 1319
  • [19] Experimental investigation of flame height and air entrainment of n-heptane double open pool fires
    Bathina, Siva K.
    Siddapureddy, Sudheer
    EXPERIMENTAL HEAT TRANSFER, 2024, 37 (04) : 356 - 366
  • [20] Investigation of sidewall height effect on the burning rate and flame tilt characteristics of pool fire in cross wind
    Chen, Xiao
    Ding, Zhiwei
    Lu, Shouxiang
    FIRE SAFETY JOURNAL, 2021, 120