Analysis of Influence of Grid-Following and Grid-Forming Static Var Generators on High-Frequency Resonance in Doubly Fed Induction Generator-Based Wind Farms

被引:1
作者
Sun, Yong [1 ]
Wu, Hongbin [2 ]
Song, Xiaozhe [3 ]
Zhang, Haifeng [4 ]
Zhang, Yifu [4 ]
Chen, Jikai [2 ]
Liu, Hongpeng [2 ]
机构
[1] Jilin Elect Power Co Ltd, Power Econ Res Inst, Changchun 130021, Peoples R China
[2] Northeast Elect Power Univ, Sch Elect Engn, Jilin 132012, Peoples R China
[3] State Grid Jilin Elect Power Co Ltd, Changchun 130021, Peoples R China
[4] State Grid Jilin Elect Power Res Inst, Changchun 130021, Peoples R China
关键词
DFIG-based wind farm; GFM control; high-frequency resonance; static var generator; sequential impedance modeling; VOLTAGE-SOURCE; STABILITY; HVDC;
D O I
10.3390/electronics13193879
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In Doubly Fed Induction Generator (DFIG)-based wind farms with Static Var Generators (SVGs), high-frequency resonance will be more like to occur when an unloaded cable is put into operation, which will threaten the stable operation of the wind farm. To address this issue, the influence of power outer loops on the impedance of grid-connected inverters is considered. Based on harmonic linearization, theoretical models for the sequence impedances of DFIGs, Grid-following (GFL) SVGs, and Grid-forming (GFM) SVGs are established. The correctness of the three models is verified by impedance scanning using the frequency sweep method. Through a comparative analysis of these sequence impedances, it is found that unlike the GFM SVG (which exhibits inductive impedance), the GFL SVG exhibits capacitive impedance in the high-frequency band, which leads to negative damping characteristics in the high-frequency band for the wind farm system with the grid-following SVG; thereby, the risk of high-frequency resonance also increases accordingly. On the contrary, GFM control adopted by SVGs can effectively eliminate the negative damping region in the high-frequency band for wind farms to suppress high-frequency resonance. Meanwhile, for grid-forming SVGs, the parameter variations in power synchronous loops have no significant impact on the suppressing effect of high-frequency resonance for wind farms. Finally, an electromagnetic simulation model for a DFIG-based wind farm system with an SVG is established using the StarSim-HIL (hardware-in-the-loop) experiment platform, and the simulation results validate the correctness of the theoretical analysis.
引用
收藏
页数:21
相关论文
共 32 条
  • [1] Development of Grid-Forming and Grid-Following Inverter Control in Microgrid Network Ensuring Grid Stability and Frequency Response
    Babu, V. Vignesh
    Roselyn, J. Preetha
    Nithya, C.
    Sundaravadivel, Prabha
    [J]. ELECTRONICS, 2024, 13 (10)
  • [2] Impedance Modeling and Analysis of Grid-Connected Voltage-Source Converters
    Cespedes, Mauricio
    Sun, Jian
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) : 1254 - 1261
  • [3] Criterion for the Electrical Resonance Stability of Offshore Wind Power Plants Connected Through HVDC Links
    Cheah-Mane, Marc
    Sainz, Luis
    Liang, Jun
    Jenkins, Nick
    Ugalde-Loo, Carlos Ernesto
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (06) : 4579 - 4589
  • [4] Overview of Mechanism and Mitigation Measures on Multi-frequency Oscillation Caused by Large-scale Integration of Wind Power
    Chi, Yongning
    Tang, Bingjie
    Hu, Jiabing
    Tian, Xinshou
    Tang, Haiyan
    Li, Yan
    Sun, Sujuan
    Shi, Lei
    Shuai, Lei
    [J]. CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2019, 5 (04): : 433 - 443
  • [5] [冯俊杰 Feng Junjie], 2020, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V40, P4805
  • [6] Gan Fanxin, 2023, Proceedings of the Chinese Society for Electrical Engineering, P7497, DOI 10.13334/j.0258-8013.pcsee.221016
  • [7] Reference-Feedforward Power-Synchronization Control
    Harnefors, Lennart
    Rahman, F. M. Mahafugur
    Hinkkanen, Marko
    Routimo, Mikko
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2020, 35 (09) : 8878 - 8881
  • [8] Hou Y., 2021, CSEE J. Power Energy Syst, V9, P1173
  • [9] High-Frequency Resonance Analysis and Reshaping Control Strategy of DFIG System Based on DPC
    Hu, Bin
    Nian, Heng
    Yang, Jun
    Li, Meng
    Xu, Yunyang
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2021, 36 (07) : 7810 - 7819
  • [10] Jansen K, 2015, 2015 IEEE EINDHOVEN POWERTECH