Effect of water mist system settings on fire and upstream smoke control in a longitudinally ventilated tunnel

被引:0
|
作者
Liu, Yuanjun [1 ]
Li, Qi [2 ]
Tang, Zhi [3 ]
Fang, Zheng [3 ]
机构
[1] Changzhou Univ, Sch Safety Sci & Engn, Changzhou 213164, Jiangsu, Peoples R China
[2] Zhongkai Univ Agr & Engn, Coll Urban & Rural Construct, Guangzhou 510225, Guangdong, Peoples R China
[3] Wuhan Univ, Sch Civil Engn, Wuhan 430072, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
Water mist system; Longitudinal ventilation; HRR; Smoke control; Tunnel fire; TEMPERATURE DISTRIBUTION; SUPPRESSION; VELOCITY; TESTS; HEAT;
D O I
10.1016/j.tust.2024.106234
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The effect of Water Mist System (WMS) settings on fire Heat Release Rate (HRR), smoke gas temperature, smoke blocking effectiveness and required critical velocity were investigated in a 3 m (width)x 2.2 m(height) x 30 m (length) tunnel model equipped with longitudinal ventilation (LV). A total of 60 tests were conducted in 12 configurations, varying the nozzles position, nozzle row number and nozzles pressure. Additionally, 5 bucket tests were also carried out to assess the influence of LV on water mist trajectories. The bucket test results revealed a strong correlation between fire HRRs and the "local" water quantity on the ground near the fire source, particularly for smaller fires. The WMS's effectiveness in reducing the maximum smoke gas temperature rise and critical velocity largely depends on the nozzles which are placed closest to the fire source to a great extent. Reducing the distance to the fire source or increasing water flow rates could both enhance the reduction effect. However, activating additional upstream nozzle rows provides minimal benefit, as the interaction between adjacent rows becomes negligible at higher LV velocities. In contrast, increasing the number of nozzle rows can enhance smoke blocking effectiveness, as measured by the confinement velocity reduction rate. The findings demonstrate that the entrainment and blockage effect of WMS are the primary determinants of the smoke back- layering (BL) degree under the confinement velocity conditions, rather than the smoke cooling effect. Furthermore, positioning the WMS upstream of the fire source and maintaining a certain distance can optimize the combined effects of WMS and LV on fire HRR and smoke back-layering control, which is partly due to the water mist deflection under ventilation flow. This preliminary study provides foundational data on fire and smoke control using water mist in longitudinally ventilated tunnels and offers insights for the optimal design of WMSs.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] Experimental study on backlayering length of thermal smoke flow in a longitudinally ventilated tunnel with blockage at upstream of fire source
    Meng, Na
    Yang, Wenyu
    Xin, Lin
    Li, Xiao
    Liu, Beibei
    Jin, Xiaona
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2018, 82 : 315 - 324
  • [2] The combined effect of a water mist system and longitudinal ventilation on the fire and smoke dynamics in a tunnel
    Liu, Yuanjun
    Fang, Zheng
    Tang, Zhi
    Beji, Tarek
    Merci, Bart
    FIRE SAFETY JOURNAL, 2021, 122
  • [3] Study on Smoke Propagation Characteristics of a Carriage Fire in Longitudinally Ventilated Tunnel
    Cong, Wei
    Cheng, Xudong
    Shi, Long
    He, Kun
    FIRE TECHNOLOGY, 2024, 60 (03) : 2231 - 2247
  • [4] FIRE SIZING IN LONGITUDINALLY VENTILATED TUNNEL
    Zhang, Qihui
    Eandi, Seamine
    Cappello, Deniele
    Astore, Giuseppe
    Grasso, Piergiorgio
    ADVANCES IN UNDERGROUND SPACE DEVELOPMENT, 2013, : 208 - 216
  • [5] Maximum smoke temperature in the longitudinally ventilated tunnel fire: Influence of the separating distance between two sources
    Ma, Xin
    Luo, Shengfeng
    Fang, Tingyong
    Wang, Jingwei
    Wan, Lulu
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2021, 107
  • [6] Effect of blockage ratio on backlayering length of thermal smoke flow in a longitudinally ventilated tunnel
    Meng, Na
    Liu, Xiaomei
    Li, Xiao
    Liu, Beibei
    APPLIED THERMAL ENGINEERING, 2018, 132 : 1 - 7
  • [7] Experimental Study on the Influence of High-Pressure Water Mist on the Ceiling Temperature of a Longitudinally Ventilated Tunnel
    Zhu, Hui
    Du, Weining
    Li, Wenfeng
    FIRE-SWITZERLAND, 2024, 7 (08):
  • [8] Coupling effect of top smoke discharging and water mist on characteristics of fire smoke
    Zhang, Pei-Hong
    Tian, Xiang-Liang
    Zhang, Yi
    Ji, Ting-Chao
    Dongbei Daxue Xuebao/Journal of Northeastern University, 2014, 35 (08): : 1199 - 1202
  • [9] Theoretical analysis on plane fire plume in a longitudinally ventilated tunnel
    Zhang, Q.
    Guo, X.
    Trussoni, E.
    Astore, G.
    Xu, S.
    Grasso, P.
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2012, 30 : 124 - 131
  • [10] Suppression on the tunnel fire by coupling the longitudinal smoke discharge and high pressure water mist
    Zhang, P.-H. (zhangpeihong@mail.neu.edu.cn), 2013, Northeast University (34):