A Simple Single-Ended Post-Fault Location Technique for DC Lines Based on Controlled Re-Energizations

被引:1
|
作者
Mahtani, Kumar [1 ]
Guerrero, Jose M. [2 ]
Decroix, Julien [3 ]
Platero, Carlos A. [1 ]
机构
[1] Univ Politecn Madrid, Escuela Tecn Super Ingn Ind, Dept Automat Elect & Elect Engn & Ind Informat, Madrid 28006, Spain
[2] Univ Basque Country, Escuela Ingn Bilbao, Dept Elect Engn, Bilbao 48013, Spain
[3] Paris Saclay Univ, Interdisciplinary Res Grp Energy Modeling, F-91190 Gif Sur Yvette, France
来源
ELECTRONICS | 2025年 / 14卷 / 02期
关键词
DC lines; fault location; inductance; injection; impedance; medium-voltage direct current; reclosing; single-ended; time constant; PULSE INJECTION; SHORT-CIRCUIT; MMC; IDENTIFICATION; SUBMODULE;
D O I
10.3390/electronics14020275
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Fault location in medium-voltage direct current (MVDC) systems is an essential yet underexplored area compared to high-voltage (HVDC) and low-voltage (LVDC) systems. MVDC systems, characterized by intermediate line lengths and fault resistances, as well as rapid fault clearance requirements, demand specialized solutions. This paper proposes a novel single-ended, offline fault location method based on controlled re-energizations after fault clearance. This approach employs a switched grounding resistor and a bypass connection through the current-limiting inductor to extract fault parameters from the discharge curves of two re-energization cycles. By analyzing the time constants derived from these curves, the method estimates fault location and resistance with high accuracy. The proposed method eliminates the need for additional active injection sources and circuit breaker modifications, ensuring seamless integration into existing MVDC infrastructure. Furthermore, the method avoids inter-terminal communication delays and sampling delays before fault clearance. Validation through electromagnetic transient simulations demonstrates fault location errors below 5% for fault resistances up to 50 Omega. Results show that the method performs better for faults farther from the active terminal, with the higher errors seen for short distances and elevated resistances. The proposed technique offers a robust and practical solution for post-fault location in DC lines.
引用
收藏
页数:25
相关论文
共 48 条
  • [21] A novel noniterative single-ended fault location method with distributed parameter model for AC transmission lines
    Duan, Mengzhao
    Liu, Yu
    Lu, Dian
    Pan, Ruiyu
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 153
  • [22] Single Ended Fault Location Method for Lines Connected with Inverter Based Renewable Resources
    Naidu, O. D.
    Aarthi, V
    Likhitha, Kukkala
    2023 IEEE PES 15TH ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE, APPEEC, 2023,
  • [23] Precise Traveling Wave-Based Transmission Line Fault Location Method Using Single-Ended Data
    Naidu, O. D.
    Pradhan, Ashok Kumar
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2021, 17 (08) : 5197 - 5207
  • [24] Single-ended Fault Location Method for Overhead Cable Mixed Lines Connected with MMC-HVDC System
    Xue S.
    Lu J.
    Wang S.
    Sun Y.
    Liu C.
    Liu B.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (22): : 103 - 111
  • [25] A parameter modification based transmission line fault location method using single-ended current
    Liu, Yuping
    He, Zhengyou
    He, Wen
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [26] Single-Ended Fault Location Method Based on Multi-Source Transient Information Fusion
    Deng F.
    Xu F.
    Zeng Z.
    Zhang Z.
    Feng S.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2022, 37 (13): : 3201 - 3212
  • [27] Single-ended data based fault location method for multi-branch distribution network
    Wang, Zixuan
    Ma, Xiao
    Lu, Yi
    Wang, Chaoliang
    Lin, Xiangning
    Sui, Quan
    ENERGY REPORTS, 2020, 6 : 385 - 390
  • [28] A Closed-Form Mathematical Model and Method for Fast Fault Location on a Low Voltage DC Feeder Using Single-Ended Measurements
    Bin Gani, Munim
    Brahma, Sukumar
    IEEE OPEN ACCESS JOURNAL OF POWER AND ENERGY, 2022, 9 : 523 - 536
  • [29] Single-ended Traveling Wave Surge Identification and Fault Location for Transmission Lines Based on the Sensitive Angle Characteristic of Waveshape With Multiple Wavefronts
    Zhang G.
    Wang K.
    Shu H.
    Si D.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2024, 44 (10): : 3789 - 3803
  • [30] A novel single-ended fault location scheme for parallel transmission lines using k-nearest neighbor algorithm
    Swetapadma, Aleena
    Yadav, Anamika
    COMPUTERS & ELECTRICAL ENGINEERING, 2018, 69 : 41 - 53