A protection scheme for the transmission line connecting large-scale centralized solar PV plant

被引:0
|
作者
Singh, Sikander [1 ]
Nayak, Paresh Kumar [1 ]
机构
[1] Indian Inst Technol, Indian Sch Mines, Dhanbad, India
来源
MICROSYSTEM TECHNOLOGIES-MICRO-AND NANOSYSTEMS-INFORMATION STORAGE AND PROCESSING SYSTEMS | 2024年
关键词
INVERTER-BASED RESOURCES; DISTANCE PROTECTION; POWER-SYSTEMS;
D O I
10.1007/s00542-024-05780-2
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The grid connected large-scale solar photovoltaic (LS-SPVP) plants affect the performance of conventional distance relays protecting the interconnected transmission line. In this paper, an improved fault detection, classification and location estimation technique is proposed for such crucial transmission lines using the line end voltage and current measurements. The method utilizes the magnitude ratios of the line end phase currents for detection and classification of the fault. The apparent power delivered to the fault from both ends of the transmission line is used further for the estimation of fault resistance. Using the estimated value of the fault resistance, the incremental impedance, the actual value of the line impedance between the relay and the fault point and the exact location of the fault is calculated. Performance of the protection technique is verified on different fault and non-fault cases simulated on a test power system as well as on the IEEE 39-bus New England system connecting a 50 MW solar PV plant using MATLAB/Simulink. The efficacy of the proposed protection scheme is also validated through OPAL-RT (OP4510) make real-time digital platform. The obtained results clearly show that using the proposed method, fast and accurate detection, classification and location estimation of even high resistance faults up to 200 Omega can be achieved in LS-SPVP connected transmission lines.
引用
收藏
页数:21
相关论文
共 46 条
  • [21] Temperature safety analysis and backup protection scheme improvement for overhead transmission line in power oscillation condition
    Wang, Jian
    Chen, Jing
    Xiong, Xiaofu
    Lu, Xiaofeng
    Liao, Zheng
    Chen, Xiaobo
    ELECTRIC POWER SYSTEMS RESEARCH, 2019, 166 : 88 - 98
  • [22] Transmission line adaptive protection scheme: A new fault detection approach based on pilot superimposed impedance
    Khoshbouy, Morteza
    Yazdaninejadi, Amin
    Bolandi, Tohid Ghanizadeh
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 137
  • [24] Co-benefits of large scale plug-in hybrid electric vehicle and solar PV deployment
    Denholm, Paul
    Kuss, Michael
    Margolis, Robert M.
    JOURNAL OF POWER SOURCES, 2013, 236 : 350 - 356
  • [25] Backup protection scheme for transmission line compensated with UPFC during high impedance faults and dynamic situations
    Kumar, Bhupendra
    Yadav, Anamika
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2017, 11 (06) : 703 - 712
  • [26] AN OBSERVER-BASED SCHEME FOR DECENTRALIZED STABILIZATION OF LARGE-SCALE SYSTEMS WITH APPLICATION TO POWER SYSTEMS
    Cordoba, Diego Langarica
    Ortega, Romeo
    ASIAN JOURNAL OF CONTROL, 2015, 17 (01) : 124 - 132
  • [27] A Dual-Time Transform Assisted Intelligent Relaying Scheme for the STATCOM-Compensated Transmission Line Connecting Wind Farm
    Biswas, Sauvik
    Nayak, Paresh
    Pradhan, Gayadhar
    IEEE SYSTEMS JOURNAL, 2022, 16 (02): : 2160 - 2171
  • [28] Protection of large-scale smart grids against false data injection cyberattacks leading to blackouts
    Khazaei, Javad
    Amini, M. Hadi
    INTERNATIONAL JOURNAL OF CRITICAL INFRASTRUCTURE PROTECTION, 2021, 35
  • [29] Reserve Requirement Impacts of Large-Scale Integration of Wind, Solar, and Ocean Wave Power Generation
    Halamay, Douglas A.
    Brekken, Ted K. A.
    Simmons, Asher
    McArthur, Shaun
    IEEE PES GENERAL MEETING, 2010,
  • [30] Flexible line ratings in stochastic unit commitment for power systems with large-scale renewable generation
    Shi, Jiaying
    Oren, Shmuel S.
    ENERGY SYSTEMS-OPTIMIZATION MODELING SIMULATION AND ECONOMIC ASPECTS, 2020, 11 (01): : 1 - 19