1-ohm Impedance Criterion for Diagnosis of Single-Phase Ground Fault of Transmission Line

被引:0
作者
Zhou, Xueming [1 ]
Wang, Xiankang [1 ]
Yao, Yao [1 ]
Feng, Zhiqiang [1 ]
Hu, Zixuan [2 ]
Fu, Jianjin [1 ]
Li, Zijian [1 ]
机构
[1] State Grid Hubei Elect Power Co Ltd, Elect Power Res Inst, Wuhan 430077, Hubei, Peoples R China
[2] North China Elect Power Univ, Sch Elect & Elect Engn, Beijing 102206, Peoples R China
来源
IEEE ACCESS | 2025年 / 13卷
关键词
High voltage transmission line; transition resistance; single-phase grounding fault; fault recorder; fault diagnosis; CLASSIFICATION; RECOGNITION;
D O I
10.1109/ACCESS.2024.3523266
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The transition resistance during single-phase grounding faults in transmission lines is closely related to the fault cause. Quickly determining the cause of the fault through the transition resistance value and taking targeted measures to restore the power supply quickly is of great significance to improving the stability of the power system. Starting from the basic circuit principle, this paper analyzes the composition of the transition resistance for two typical grounding situations: the line-to-tower discharge and the line-to-ground discharge, and derives the equivalent impedance of the tower-wire grounding system. Based on analyzing the grounding wire parameters, the tower grounding resistance, and the span size, the 1-ohm impedance criterion was proposed, that is, the transition resistance during line-to-tower discharges should be less than 1 ohm. Then, the equation for calculating the transition resistance using the double-terminal fault recording was derived and simplified for engineering calculation. Finally, combined with 56 real fault cases of 220 kV similar to 1000 kV transmission lines, each case's transition resistance value and fault cause are analyzed to verify the effectiveness of the proposed 1-ohm criterion.
引用
收藏
页码:1680 / 1687
页数:8
相关论文
共 29 条
  • [1] Fault location and detection techniques in power distribution systems with distributed generation: Kenitra City (Morocco) as a case study
    Azeroual, Mohamed
    Boujoudar, Younes
    Bhagat, Kalsoom
    El Iysaouy, Lahcen
    Aljarbouh, Ayman
    Knyazkov, Alexey
    Fayaz, Muhammad
    Qureshi, Muhammad Shuaib
    Rabbi, Fazle
    EL Markhi, Hassane
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2022, 209
  • [2] A Decentralized Fault Detection Technique for Detecting Single Phase to Ground Faults in Power Distribution Systems With Resonant Grounding
    Barik, Md. Abdul
    Gargoom, Ameen
    Mahmud, Md. Apel
    Haque, Md. Enamul
    Al-Khalidi, Hassan
    Oo, Amanullah Maung Than
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2462 - 2473
  • [3] Bhongade S, 2016, 2016 INTERNATIONAL CONFERENCE ON ELECTRICAL POWER AND ENERGY SYSTEMS (ICEPES), P151, DOI 10.1109/ICEPES.2016.7915922
  • [4] Identify Direct Lightning Strike Location Based on Discrete Wavelet Transform for 115-kV Transmission System
    Chiradeja, Pathomthat
    Ngaopitakkul, Atthapol
    [J]. IEEE ACCESS, 2022, 10 : 80609 - 80622
  • [5] Hilbert-Transform-Based Transient/Intermittent Earth Fault Detection in Noneffectively Grounded Distribution Systems
    Cui, Tao
    Dong, Xinzhou
    Bo, Zhiqian
    Juszczyk, Andrzej
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) : 143 - 151
  • [6] Ground distance relay compensation based on fault resistance calculation
    Eissa, M. M.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (04) : 1830 - 1835
  • [7] Accurate Single-Phase Fault-Location Method for Transmission Lines Based on K-Nearest Neighbor Algorithm Using One-End Voltage
    Farshad, Mohammad
    Sadeh, Javad
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) : 2360 - 2367
  • [8] Fault Classification and Detection by Wavelet-Based Magnetic Signature Recognition
    Franca Sartori, Carlos Antonio
    Sevegnani, Francisco Xavier
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 2010, 46 (08) : 2880 - 2883
  • [9] Statistical Design of Experiments for Power System Protection Testing: A Case Study for Distance Relay Performance Testing
    Ginocchi, Mirko
    Penthong, Thanakorn
    Ponci, Ferdinanda
    Monti, Antonello
    [J]. IEEE ACCESS, 2024, 12 : 27052 - 27072
  • [10] Typical Fault Cause Recognition of Single-Phase-to-Ground Fault for Overhead Lines in Nonsolidly Earthed Distribution Networks
    Liang, Yong-Liang
    Li, Ke-Jun
    Ma, Zhao
    Lee, Wei-Jen
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2020, 56 (06) : 6298 - 6306